Outback FX-R Series Technical Note on Input Modes
Application Note
©2015OutBackPowerTechnologies,Arlington,WA98223MAM‐9/21/15Page8of10
cycle life. So for three strings of OutBack 200RE batteries about 1500 W minimum AC
load, or 30 Adc is best.
2. Be sure the RE kWh exceeds the load kWh or the batteries may be chronically
undercharged as the batteries compete with the loads for power to recharge themselves.
The RE kWh minus the load kWh must equal enough charging current during the RE
period to properly charge the batteries.
3. The RE kWh must be more than the load kWh, but not so much that the maximum
battery bank charging current is exceeded. For example, a 4kW Radian/FXR inverter
with a 4kW PV array into an FM80 charge controller will produce a maximum current of
80 Adc. If the DoD Amps is set to 7 Aac, this would result in a 32 Adc draw from the DC
bus (minimum suggested per guideline #1), which leaves 48 Adc for charging the battery
bank. This is too much for a single string of OutBack 200RE batteries, and a little on the
high side. It is all right for two strings, and just about right for three strings. If a larger
array is going to be used, then Li Ion batteries would be a good choice as they can be
charged and discharged rapidly with very little consequence.
Mini Grid Mode
The normal operation of Mini Grid is for the inverter and loads to be disconnected from the grid
and power the loads with PV power and/or stored energy from the battery. Unlike Grid Zero, the
rate of discharge from the battery is not controlled. Grid power is not blended with PV power
unless it’s in Offset mode while charging the batteries. However, similar to Grid Zero, the Mini
Grid mode works best when there is more PV power kWh than load demand kWh as it only
connects to the grid when the battery hits a user selectable low-battery setting. As long as there
is adequate active PV power and stored PV power in the batteries to power the loads, then Mini
Grid will never connect to the grid. If the low battery setting is reached for the delay period
specified, then the Radian/FXR connects to the grid and it will power the loads. If the
Radian/FXR charger is turned on, then the batteries will complete a full charge cycle from the
grid (a partial charge cycle can also be specified). The inverter will not disconnect from the grid
until adequate PV power is available, or achieves one of the three DC voltage targets (see
Offset application note). If the Radian/FXR charger is turned off, then the grid will power the
loads on reaching the low-battery setting, but will not charge the batteries from the grid. The
Radian/FXR will not disconnect from the grid and start powering loads with PV power until
adequate PV power is available for charging the batteries and powering the loads. Follow the
same battery sizing guidelines listed above under Grid Zero.