Quick Start Guide
MATE RTS
CB
3
CB
2
CB
1
CB
6
CB
5
CB
4
CB
8
CB
7
CB
10
CB
9
CB
12
CB
11
CB
14
CB
13
CB
16
CB
15
GND
AC IN
DC
POSITIV
E
I/ON
I/ON
I/ON I/ONI/ONI/ON
NORMAL
UP
DOWN
BYPASSED
O/
OFF
O/
OFF
GND
DC
NEGATIVE
SHUNT A
SHUNT C
SHUNT B
AC IN
DC
AC OUT
AC IN
DC
AC
OUT
MATE RTS
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND/
PE
CHASSIS GROUND/
PE
AC NEUTRAL IN
AC HOT IN
MATE RTS
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND/
PE
CHASSIS GROUND/
PE
AC NEUTRAL IN
AC HOT IN
MASTER
BYPASS
SLAVE L2
BYPASS
MASTER
OUTPUT
SLAVE
L2
OUTPUT
MASTER
INPUT
SLAVE
L2
INPUT
250
ON
250
ON
OFF
O
SLAVE L2
INVERTER
MASTER
INVERTER
PV
ARRA
Y
PV
ARRA
Y
FNDC
OFF
O
OFF
O
GROUND
FAULT
Charge
Controlle
r
Charge
Controller
OFF
O
O
F
F
O
FAULT
PV
INACTIVE
NORMAL
PV ACTIVE
PV ARRAY
GROUND
FAULT
DETECTOR
INTERRUPTE
R
Energize/Startup
Procedures
Pre-startup Procedures:
After opening the AC and DC enclosures:
1. Double-check all wiring connections.
2. Inspect the enclosure to ensure no tools
or debris has been left inside.
3. Disconnect AC loads at the load panel.
4. Disconnect AC inputs at the source.
5. Place the mechanical interlock in the
normal (non-bypass) position.
Functional Test
Points
Battery Voltage Test Points
AC IN Voltage Test Points
(Terminal bus bar = TBB)
AC OUT Voltage Test Points
(Terminal bus bar = TBB)
De-energize/Shutdown
Procedures
WARNING: Lethal Voltage
Review the system configuration to identify
all possible sources of energy. Ensure ALL
sources of power are disconnected before
performing any installation or maintenance
on this equipment. Confirm that the
terminals are de-energized using a
validated voltmeter (rated for a minimum
1000 Vac and 1000 Vdc) to verify the
de-energized condition.
WARNING: Lethal Voltage
The numbered steps will remove power from
the inverter and charge controllers.
However, sources of energy may still be
present in the AC and DC wiring boxes. To
ensure absolute safety, disconnect ALL
power connections at the source.
WARNING: Burn Hazard
Internal parts can become hot during
operation. Do not remove the cover during
operation or touch any internal parts.
Be sure to allow the parts sufficient time to
cool down before attempting to perform
any maintenance.
To de-energize or shut down the OutBack devices:
1. Turnoff(open)theACcircuitbreakers.
2. Turnoff(open)theDCcircuitbreakersforthebattery.
Wait5minutesforthedevicestointernallydischargethemselves.
3. Turnoff(open)thePVcircuitbreakers.
4. Turnoff(open)theGFDIcircuitbreaker.
5. Verify0VdcontheDCinputterminalofthemasterinv
erterbyplacingthe
voltm
eterleadsonand.
6. Verify0VdcontheDCinputterminaloftheslaveinverterbyplacingthe
voltmeterleadsonand.
7. Verify0VdconthePVterminalsofonechargecontrollerbyplacingthe
voltmeterleadsonand.
8. Verify0VdconthePVterminal
softheotherchargecontrollerbyplacingthe
voltmeterleadsonand.
9. Verify0VacontheACoutputcircuitbreakersbyplacingthevoltmeterleads
onand.
900-0158-01-00 REV B.vsd
©2013 OutBack Power Technologies. All Rights Reserved.
1b 1c
1
1b
1a
1
2
3
4
2
4
2a
2c
5
3
4
2
4
5
3
43
3
5
PV Voltage Test Points
1
3
CAUTION: Equipment Damage
Incorrect battery polarity will damage the equipment.
1
1d
1b 1d
2e2b
2d 2f
Test points 2a and
2c refer to the
bottom terminal of
the circuit
breakers.
1b1a 1c 1d
2a 2b 2c 2d 2f2e
1c
2e
2b
2f
2d
2
53
To energize or start up the OutBack devices:
1. Using a digital voltmeter (DVM), verify 12, 24, or 48 Vdc on the DC input terminals by placing
the DVM leads on and . Confirm that the voltage is correct for the inverter and charge
controller models. Confirm the polarity.
2. Verify that the PV output for each charge controller is in the correct range of open-circuit
voltage and confirm the polarity by:
a) placing the DVM leads on and , and
b) placing the DVM leads on and .
3. Verify 230 Vac on the terminals of the AC source and connect the source.
4. Verify 230 Vac on the AC Input TBB by placing the DVM leads on and .
7. Turn on (close) the GFDI circuit breaker.
8. Turn on (close) the PV input circuit breakers.
9. Turn on (close) the DC circuit breakers from the battery bank to the inverter.
10. Check the system display or LED indicators. Ensure the inverter is in the ON state.
The factory default state for FXR inverters is OFF.
11. Turn on (close) the FN-DC circuit breaker.
12. Turn on (close) the AC output circuit breakers.
13. Verify 230 Vac on the AC Output TBB by placing the DVM leads on and .
NOTE: Assumes correct stacking programming with the Configuration Wizard.
16. Replace the covers on the AC and DC enclosures.
17. Turn on (close) the AC input circuit breakers.
18. Turn on the AC disconnects at the load panel and test the loads.