FLEXmax 60/80 SPECIFICATIONS 04/2017E
Models
*
:
FLEXmax 80 (FM80-150VDC) FLEXmax 60 (FM60-150VDC)
Nominal Battery Voltages
12, 24, 36, 48, or 60VDC (Single model, selectable via eld programming at start-up) 12, 24, 36, 48, or 60VDC (Single model, selectable via eld programming at start-up)
Maximum Output Current
80A @ 104°F (40°C) with adjustable current limit 60A @ 104°F (40°C) with adjustable current limit
NEC Recommended Solar
Maximum Array STC Nameplate
12VDC systems: 1000W / 24VDC systems: 2000W
48VDC systems: 4000W / 60VDC systems: 5000W
12VDC systems: 750W / 24VDC systems: 1500W
48VDC systems: 3000W / 60VDC systems: 3750W
PV Open Circuit Voltage (VOC)
150VDC absolute maximum coldest conditions / 145VDC start-up and operating maximum 150VDC absolute maximum coldest conditions / 145VDC start-up and operating maximum
Standby Power Consumption
Less than 1W typical Less than 1W typical
Power Conversion Eciency
97.5% @ 80ADC in a 48VDC System (typical) 98.1% @ 60ADC in a 48VDC System (typical)
Peak Eciency
60VDC input w/48V battery at 53.1VDC (98.44%) 68VDC input w/48V battery at 52.8VDC (98.31%)
Charging Regulation
Bulk, absorption, oat, silent and equalization Bulk, absorption, oat, silent and equalization
Voltage Regulation Set points
13 to 80VDC user adjustable with password protection 13 to 80VDC user adjustable with password protection
Equalization Charging
Programmable voltage setpoint and duration, automatic termination when completed Programmable voltage setpoint and duration, automatic termination when completed
Battery Temperature Compensation
Automatic with optional RTS installed / 5.0mV per °C per 2V battery cell Automatic with optional RTS installed / 5.0mV per °C per 2V battery cell
Voltage Step-Down Capability
Down convert from any acceptable array voltage to any battery voltage. Example: 72VDC array to 24VDC battery; 60VDC array to 48VDC battery
Programmable Auxiliary Control Output
12VDC output signal which can be programmed for dierent control applications (maximum of 0.2ADC)
Status Display
3.1” (8 cm) backlit LCD screen, 4 lines with 80 alphanumeric characters total 3.1” (8 cm) backlit LCD screen, 4 lines with 80 alphanumeric characters total
Remote Display and Controller
Optional MATE3, MATE or MATE2 Optional MATE3, MATE or MATE2
Network Cabling
Proprietary network system using RJ-45 modular connectors with CAT5 cable (8 wires) Proprietary network system using RJ-45 modular connectors with CAT5 cable (8 wires)
Data Logging
Last 128 days of operation: amp-hours, watt-hours, time in oat, peak watts, amps, solar array voltage, maximum battery voltage, min. battery voltage and absorb time, accumulated amp-hours,
and kWh of production
Operating Temperature Range
-40 to 60°C (power automatically derated above 40°C) -40 to 60°C (power automatically derated above 40°C)
Environmental Rating
Indoor Type 1 Indoor Type 1
Conduit Knockouts
One 1” (25.4mm) on the back; One 1” (25.4mm) on the left side; Two 1” (25.4mm) on the bottom One 1” (25.4mm) on the back; One 1” (25.4mm) on the left side; Two 1” (25.4mm) on the bottom
Warranty
Standard 5-year / Available 10-year Standard 5-year / Available 10-year
Weight (lb/kg)
Unit: 12.20 / 5.53
Shipping: 15.5 / 7
Unit: 11.65 / 5.3
Shipping: 14.9 / 6.8
Dimensions H x W x D (in/cm)
Unit: 16.25 x 5.75 x 4.5 / 41.3 x 14.6 x 11.4
Shipping: 19 x 9.5 x 8.5 / 48.3 x 24.1 x 21.6
Unit: 13.75 x 5.75 x 4.5 / 35 x 14.6 x 11.4
Shipping: 17 x 9.5 x 8.5 / 43.2 x 24.1 x 21.6
Options
Remote Temperature Sensor (RTS), HUB4, HUB10.3, MATE, MATE2, MATE3 Remote Temperature Sensor (RTS), HUB4, HUB10.3, MATE, MATE2, MATE3
Menu Languages
English & Spanish English & Spanish
Certications
ETL Listed to UL1741, CSA C22.2 No. 107.1 ETL Listed to UL1741, CSA C22.2 No. 107.1
*Use appropriate wire size in accordance with NEC.
Low Voltage Charge Controller Advantage—Smaller string size reduces power output loss in the event of inadvertent module shading
OutBack FLEXmax 80 Charge Controller
Lower Voltage Four-String, 3780W Array (315W Modules)
Shading of a single module aects one string, resulting in a
power output loss of up to 25%
Competitor Charge Controller
Higher Voltage Two-String, 3780W Array (315W Modules)
Shading of a single module aects one string, resulting in a
power output loss of up to 50%