Flexnet Specifications

BATTERY
BBUS
SHUNT C
SHUNT A
SHUNT B
net DC
TM
SOURCES
INVERTER
Available From:
Corporate Ofce:
19009 62nd Avenue NE
Arlington, WA 98223 USA
Phone: (360) 435.6030
Fax: (360) 435.6019
FN-DC Specications
Battery Voltage Input Range 8.0 to 80.0 Volts DC
Battery Voltage Resolution 0.1 Volts DC
Number of Current Channels One to Three (each can be a Source or Load)
Current Range (Each Channel) -1000.0 Amps to +1000.0 Amps DC
Current Resolution 0.1 Amps DC
State of Charge Display 0 to 100% (1% increments)
Aux Relay Configuration SPST, Magnetic Latching Relay
Aux Relay Max Rating 5 Amps @ 30 Volts DC
Current Shunt Type (order separately) 500 Amp / 50mv
Display Primary OutBack Power MATE or MATE2 4 x 20 LCD
Secondary Five LED Indicators on front of FLEXnet DC
Battery AH Capacity Range 100 to 10,000 Amp Hours
Data Logging Memory Most recent 128 Days
Programmable AUX Relay Settings Battery Volts Adjustable from 8.0 to 80.0 VDC
State of Charge Adjustable from 0 to 100%
Time Delay Adjustable from 0 to 240 Minutes
Accuracy 0.5% of Reading +/- 2 LSDs per channel
Operating Temperature Range 0 - 50
º
C
Mounting 3/4” Panel Mount Breaker Slot or Surface Mount
Warranty Standard 2 year
Weight Unit 5 oz. (.142kg)
Shipping 2 lbs. (.907 kg)
Dimensions (H x W x L) Unit 0.74 x 3.72 x 6.60” (1.88 x 9.45 x 16.75 cm)
Shipping 2.13 x 9 x 11.5” (5.4 x 22.86 x 29.21 cm)
European Ofce:
Barcelona, ESPAÑA
Phone: (+34) 600.843.845
www.outbackpower.com
Additional Available Data
Total Battery Amps
Averaged Battery Amps
Averaged Battery Volts
DC Amp-Hours IN Per Shunt
DC Amp-Hours OUT Per Shunt
DC kWh IN Per Shunt
DC kWh OUT Per Shunt
Last Cycle Amp Hours
Last Cycle Watt Hours
Last Cycle Amp Hour Charge Factor
Last Cycle Watt Hour Charge Eciency
Total Number of Days Full
Cumulative Battery Amp Hours Removed
Sample Multi-Shunt Conguration