Outback FM80 User Manual
Operation
900-0009-01-00 Rev D 55
Auto ReStart (Advanced Menu)
This setting allows the user to choose between continuous maximum power point (MPP)
tracking, or occasional restarts of the sweeping process. A restart means the controller
abandons the existing maximum power point value it was using and “re-sweeps”, or begins
gathering new power point data. (See page 97 for more information on MPP tracking.)
Auto ReStart has three options available:
o
Mode 0
– Initial sweep only and then continuous MPP tracking.
Auto ReStart
is disabled.
The FLEXmax will continously track the maximum power point without starting over.
o
Mode 1
– Automatic re-sweep every 90 minutes if controller is in an MPPT mode (
MPPT Float
,
MPPT Bulk
, etc). This will not reset any counters, charging stages, or statistics.
o
Mode 2
– Automatic re-sweep every 90 minutes if controller is in any charging mode. This will not
reset any counters, charging stages, or statistics.
Figure 45 Auto ReStart
ADVANCED MENU
Auto ReStart
MODE 0
EXIT NEXT MODE
Auto ReStart
Screen
To select an Auto ReStart mode:
1. Navigate to the Auto ReStart screen through the
ADVANCED MENU as instructed in Figure 35.
2. Press <MODE> to switch between the three Auto ReStart
modes: MODE 0 (default), MODE1, and MODE2.
ADVANCED MENU
Auto ReStart
Mode 0
EXIT NEXT MODE
ADVANCED MENU
Auto ReStart
MODE 1
EXIT NEXT MODE
ADVANCED MENU
Auto ReStart
MODE 2
EXIT NEXT MODE
To Exit:
o Press <NEXT> to advance to the Aux Polarity screen.
o Press <EXIT> once to return to the main menu.
o Press <EXIT> twice to return to the status screen.