Outback FM80 User Manual

Applications
900-0009-01-00 Rev D 103
Figure 102 Adjusting Range Limits for Hydroelectric
or Fuel-cell Applications
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
Main Menu
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
ADV SETU
P
Screen
ADVANCED MENU
MPPT Mode
Auto Track
EXIT NEXT nonGT MODE
MPPT
Mode (Auto Track)
To adjust the Lower Mpp Range Limit:
1. From the main menu, press <> to move the arrow
next to the Advanced function.
2. Press <GO>.
3. In the ADVANCED MENU screen, press <NEXT>
again to display the Mpp Range Limit % Voc screen.
4. Press <1/2> until FULL appears.
5. When finished, press <NEXT> until the MPPT Mode
screen appears.
ADVANCED MENU
Park Mpp
Watts 0251 77 % Voc
EXIT NEXT -% +%
U-pick% (Voc)
MPPT Mode
ADVANCED MENU
Mpp Range Limit %VOC
Min Max
EXIT NEXT 1/2 90%
M
pp
Ran
g
e Limit % Vo
c
ADVANCED MENU
Snooze Mode
< 0.6 amp
EXIT NEXT AMP
To pick between Auto Track or U-Pick % MPPT Mode and determine
the charge controller’s operating V
oc
percentage, press <MODE> to
interchange between the two modes.
Re-entering the password might be required. After choosing a mode,
press <NEXT> in the ADVANCED MENU to view the Park Mpp screen
(only applicable for U-Pick mode).
Press < –%> or <+%> to select one of the percentage values; U-Pick
always uses the Park Mpp value.