Outback FM80 Specifications

2
OutBack Power Technologies, Inc. 1628 W Williams Drive, Phoenix, AZ 85027
Tel: +1 360 435 6030 Technical Support: +1 360 618 4363 Email: sales@outbackpower.com
For more information visit www.outbackpower.com
© 2021 OutBack Power Technologies, Inc. All Rights Reserved. Trademarks and logos are the property of Alpha Technologies Services, Inc.,
EnerSys and its affiliates unless otherwise noted. Subject to revisions without prior notice. E. & O.E.
Models*: FLEXmax 80 (FM80 to 150VDC) FLEXmax 60 (FM60 to 150VDC)
Nominal Battery Voltages:
12, 24, 36, 48, or 60VDC (Single model, selectable via field programming at start-up) 12, 24, 36, 48, or 60VDC (Single model, selectable via field programming at start-up)
Maximum Output Current:
80A @ 104°F (40°C) with adjustable current limit 60A @ 104°F (40°C) with adjustable current limit
NEC Recommended Solar
Maximum Array STC Nameplate:
12VDC systems: 1000W / 24VDC systems: 2000W
48VDC systems: 4000W / 60VDC systems: 5000W
12VDC systems: 750W / 24VDC systems: 1500W
48VDC systems: 3000W / 60VDC systems: 3750W
PV Open Circuit Voltage (VOC):
150VDC absolute maximum coldest conditions / 145VDC start-up and operating maximum 150VDC absolute maximum coldest conditions / 145VDC start-up and operating maximum
Standby Power Consumption:
Less than 1W typical Less than 1W typical
Power Conversion Efficiency:
97.5% @ 80ADC in a 48VDC system (typical) 98.1% @ 60ADC in a 48VDC system (typical)
Peak Efficiency:
60VDC input w/48V battery at 53.1VDC (98.44%) 68VDC input w/48V battery at 52.8VDC (98.31%)
CEC Weighted Efficiency:
97.2% (at 48VDC) 97.4% (at 48VDC)
Charging Regulation:
Bulk, absorption, float, silent and equalization Bulk, absorption, float, silent and equalization
Voltage Regulation Set Points:
13 to 80VDC user adjustable with password protection 13 to 80VDC user adjustable with password protection
Equalization Charging:
Programmable voltage setpoint and duration, automatic termination when completed Programmable voltage setpoint and duration, automatic termination when completed
Battery Temperature Compensation:
Automatic with optional RTS installed / 5.0mV per °C per 2V battery cell Automatic with optional RTS installed / 5.0mV per °C per 2V battery cell
Voltage Step-Down Capability:
Down convert from any acceptable array voltage to any battery voltage. Example: 72VDC array to 24VDC battery; 60VDC array to 48VDC battery
Programmable Auxiliary Control Output:
12VDC output signal which can be programmed for different control applications (maximum of 0.2ADC) 12VDC output signal which can be programmed for different control applications (maximum of 0.2ADC)
Status Display:
3.1in (8cm) backlit LCD screen, 4 lines with 80 alphanumeric characters total 3.1in (8cm) backlit LCD screen, 4 lines with 80 alphanumeric characters total
Remote Display and Controller:
Optional MATE3s, MATE or MATE2 Optional MATE3s, MATE or MATE2
Network Cabling:
Proprietary network system using RJ-45 modular connectors with CAT5 cable (8 wires) Proprietary network system using RJ-45 modular connectors with CAT5 cable (8 wires)
Data Logging:
Last 128 days of operation: amp-hours, watt-hours, time in float, peak watts, amps, solar array voltage, maximum battery voltage, minimum battery voltage and absorb time, accumulated amp-hours,
and kWh of production
Operating Temperature Range:
–40 to 60°C (power automatically derated above 40°C) –40 to 60°C (power automatically derated above 40°C)
Environmental Rating:
Indoor Type 1 Indoor Type 1
Conduit Knockouts:
One 1in (25.4mm) on the back; One 1in (25.4mm) on the left side; Two 1in (25.4mm) on the bottom One 1in (25.4mm) on the back; One 1in (25.4mm) on the left side; Two 1in (25.4mm) on the bottom
Warranty:
Standard 5 year, extended 10 year available Standard 5 year, extended 10 year available
Weight (lb/kg):
Unit: 12.20 / 5.53 Shipping: 15.5 / 7 Unit: 11.65 / 5.3 Shipping: 14.9 / 6.8
Dimensions H x W x D (in/cm):
Unit: 16.25 × 5.75 × 4.5 / 41.3 × 14.6 × 11.4 Shipping: 19 × 9.5 × 8.5 / 48.3 × 24.1 × 21.6 Unit: 13.75 × 5.75 × 4.5 / 35 × 14.6 × 11.4 Shipping: 17 × 9.5 × 8.5 / 43.2 × 24.1 × 21.6
Options:
Remote Temperature Sensor (RTS), HUB4, HUB10.3, MATE, MATE2, MATE3s Remote Temperature Sensor (RTS), HUB4, HUB10.3, MATE, MATE2, MATE3s
Menu Languages:
English and Spanish English and Spanish
Certifications:
ETL Listed to UL1741, CSA C22.2 No. 107.1 ETL Listed to UL1741, CSA C22.2 No. 107.1
FLEXmax 60/80 Specifications
02/2021
#980-00080-01-001 REV B
*Use appropriate wire size in accordance with NEC.
Low Voltage Charge Controller Advantage—Smaller string size reduces power output loss in the event of inadvertent module shading
OutBack Power FLEXmax 80 Charge Controller
Lower Voltage Four-String, 3780W Array (315W Modules)
Shading of a single module affects one string, resulting in a
power output loss of up to 25%
Competitor Charge Controller
Higher Voltage Two-String, 3780W Array (315W Modules)
Shading of a single module affects one string, resulting in a
power output loss of up to 50%