Alino Datasheet
OutBack Power reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2019 OutBack Power. All Rights Reserved. OutBack Power is a registered trademark of Alpha Technologies Services, Inc.
2
Alino Specifications 08/2019
www.outbackpower.com
#980-00074-01-001 REV A
50Hz 60Hz
Models:
APCU 1424 APCU 2648 APCU 3348 APCU 1424A APCU 1424B APCU 2648A APCU 2648B
Parameters
Type
Single-phase solar power conditioning unit Single-phase solar power conditioning unit
Nominal Battery Voltage
24VDC 48VDC 48VDC 24VDC 24VDC 48VDC 48VDC
Nominal Power Rating (25°C)
1400VA 2600VA 3300VA 1400VA 1400VA 2600VA 2600VA
Nominal Output
230VAC/50Hz 230VAC/50Hz 230VAC/50Hz 120VAC/60Hz 220VAC/60Hz 120VAC/60Hz 220VAC/60Hz
Electrical—Solar
Charger Technology
MPPT MPPT MPPT MPPT MPPT MPPT MPPT
PV Charge Controller Rating
1kW
p
2kW
p
2.5kW
p
1kW
p
1kW
p
2kW
p
2kW
p
Battery Input Range
18 to 32VDC 36 to 64VDC 36 to 64VDC 18 to 32VDC 18 to 32VDC 36 to 64VDC 36 to 64VDC
Absolute Maximum VOC
55VDC 100VDC 100VDC 55VDC 55VDC 100VDC 100VDC
Operating Voltage Lmit
50VDC 90VDC 90VDC 50VDC 50VDC 90VDC 90VDC
MPPT Range
26 to 40VDC 48 to 72VDC 48 to 72VDC 26 to 40VDC 26 to 40VDC 48 to 72VDC 48 to 72VDC
Panel High Voltage Cut-Off
>50VDC >90VDC >90VDC >50VDC >50VDC >90VDC >90VDC
Recommended PV Panel
72 & 60 cells 72 & 60 cells 72 & 60 cells 72 & 60 cells 72 & 60 cells 72 & 60 cells 72 & 60
Recommended PV Panel Configuration
1 panel per string and
4 panels in parallel
2 panels in series per string
and 4 panels in parallel
2 panels in series per string
and 5 panels in parallel
1 panel per string and
4 panels in parallel
1 panel per string and
4 panels in parallel
2 panels in series per string
and 4 panels in parallel
2 panels in series per string
and 4 panels in parallel
Maximum Charging Current
40A 40A 40A 40A 40A 40A 40A
Charger Efficiency
>95% >95% >95% >95% >95% >95% >95%
MPPT Tracking Efficiency
>99% >99% >99% >99% >99% >99% >99%
Charging Modes
Four modes (bulk/absorption/float/equalization) Four modes (bulk/absorption/float/equalization)
Battery Type Selection
Default flooded or sealed maintenance-free (VRLA/GEL/AGM),
selectable through front panel
Default flooded or sealed maintenance-free (VRLA/GEL/AGM),
selectable through front panel
Battery High Cut-Off
>32VDC >64VDC >64VDC >32VDC >32VDC >64VDC >64VDC
Type of Cooling
Forced Forced Forced Forced Forced Forced Forced
Electrical—Grid
Input Voltage Range
145 to 275VAC 145 to 275VAC 145to 275VAC 75 to 143VAC 145 to 265VAC 75 to 143VAC 145 to 265VAC
Input Frequency Range
42 to 58Hz 42 to 58Hz 42 to 58Hz 55 to 65Hz 55H to 65Hz 55 to 65Hz 55 to 65Hz
AVR Input Range (Beyond Given Input Range,
AVR Output Regulation is ±20%)
165 to 275VAC 165 to 275VAC 165 to 275VAC 85 to 143VAC 165 to 265VAC 85 to 143VAC 165 to 265VAC
AVR Output Range
230VAC ± 10% 230VAC ± 10% 230VAC ± 10% 120VAC ± 10% 220VAC ± 10% 120VAC ± 10% 220VAC ± 10%
Typical Frequency
50Hz 50Hz 50Hz 60Hz 60Hz 60Hz 60Hz
Battery Charging Current from Mains
Up to 20A Up to 20A Up to 20A Up to 20A Up to 20A Up to 20A Up to 20A
Transfer Time (Utility/Generator to Inverter)