OutBackPower FXR Renewable Series 230V E Model Operator’s Manual
Specifications
76 900-0169-01-00 Rev B
Table 24 FXR Settings for 48-Volt Models
Field Item Default Minimum Maximum
INVERTER
Hot Key
Inverter Mode Off On, Off, or Search
CHARGER
Hot Key
Charger Control On On or Off
AC Input
Hot Key
AC Input Mode
Use Drop or Use
Search
Sensitivity (see page 24 for increments)
30 0 200
Pulse Length
8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spacing
60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Type Grid Grid or Gen
Charger Control On On or Off
Grid Input AC Limit
30 Aac 5 Aac 55 Aac
Gen Input AC Limit
30 Aac 5 Aac 55 Aac
Charger AC Limit
FXR2348E 6 Aac 0 Aac 7 Aac
VFXR3048E 9 Aac 0 Aac 10 Aac
Grid AC Input
Mode and Limits
Input Mode Support
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac 170 Vac 230 Vac
(Voltage Limit) Upper
252 Vac 232 Vac 290 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
0.2 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
50.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
FXR2348E 6 Aac 0.5 Aac 12 Aac
VFXR3048E 6 Aac 0.5 Aac 15 Aac
Gen AC Input
Mode and Limits
Input Mode Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
208 Vac 170 Vac 230 Vac
(Voltage Limit) Upper
252 Vac 232 Vac 290 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
0.5 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
50.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
FXR2348E 6 Aac 0.5 Aac 12 Aac
VFXR3048E 6 Aac 0.5 Aac 15 Aac
AC Output
Output Voltage X
230 Vac 200 Vac 260 Vac
Low Battery
Cut-Out Voltage
42.0 Vdc 36.0 Vdc 48.0 Vdc
Cut-In Voltage
50.0 Vdc 40.0 Vdc 56.0 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc 44.0 Vdc 64.0 Vdc
(Absorb) Time
1.0 hours 0.0 hours 24.0 hours
Float Voltage
54.4 Vdc 44.0 Vdc 64.0 Vdc
(Float) Time
1.0 hours 0.0 hours 24/7
Re-Float Voltage
50.0 Vdc 44.0 Vdc 64.0 Vdc
Re-Bulk Voltage
48.0 Vdc 44.0 Vdc 64.0 Vdc
Battery Equalize
Equalize Voltage
58.4 Vdc 44.0 Vdc 68.0 Vdc
(Equalize) Time
1.0 hours 0.0 hours 24.0 hours