OutBackPower FXR Renewable Series 230V E Model Operator’s Manual

Specifications
900-0169-01-00 Rev B 75
Table 23 FXR Settings for 24-Volt Models
Field Item Default Minimum Maximum
Auxiliary Output
Aux Control Auto Off, Auto or On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
28.0 Vdc 20.0 Vdc 36.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt <
22.0 Vdc 20.0 Vdc 36.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt <
22.0 Vdc 20.0 Vdc 36.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt >
28.0 Vdc 20.0 Vdc 36.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
28.0 Vdc 20.0 Vdc 36.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt >
28.0 Vdc 20.0 Vdc 36.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
22.0 Vdc 20.0 Vdc 36.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt >
28.0 Vdc 20.0 Vdc 36.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
22.0 Vdc 20.0 Vdc 36.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode Master Master, Slave, B Phase Master, C Phase Master
Power Save
Ranking
Mode = Master: Master Power Save Level
0 0 10
Mode = Slave: Slave Power Save Level
1 1 10
Grid-Tie Sell
Offset Enable Y Y or N
Sell Voltage
26.0 Vdc 22.0 Vdc 32.0 Vdc
Calibrate
AC Input Voltage X
0 Vac –7 Vac 7 Vac
AC Output Voltage X
0 Vac –7 Vac 7 Vac
Battery Voltage
X
0.0 Vdc –0.4 Vdc 0.4 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency X
50 Hz 50 Hz, 60 Hz
Stage 1 Voltage Trip
Over Voltage Clearance Time X
1.5 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip X
252 Vac 240 Vac 300 Vac
Under Voltage Clearance Time X
1.5 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip X
208 Vac 160 Vac 240 Vac
Stage 2 Voltage Trip
Over Voltage Clearance Time X
0.2 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip X
264 vac 240 Vac 300 Vac
Under Voltage Clearance Time X
0.2 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip X
196 Vac 160 Vac 240 vac
Frequency Trip
Over Frequency Clearance Time X
0.2 seconds 0.12 seconds 5.0 seconds
Over
Frequency Trip
60-Hz system
X
61.0 Hz 60.2 Hz 65.0 Hz
50-Hz system 51.0 Hz 50.2 Hz 55.0 Hz
Under Frequency Clearance Time X
0.2 seconds 0.12 seconds 5.0 seconds
Under
Frequency Trip
60-Hz system
X
57.0 Hz 55.0 Hz 59.8 Hz
50-Hz system 47.0 Hz 45.0 Hz 49.8 Hz
Mains Loss
Clearance Time X
2.0 seconds 1.0 seconds 25.0 seconds
Reconnect Delay X
60 seconds 2 seconds 302 seconds
Multi-Phase Coordination
Coordin. AC Connect/Disconn.
N Y or N
Sell Current Limit
Maximum Sell
Current
FXR2024E
X
10 Aac 2.5 Aac 10 Aac
VFXR3024E 10 Aac 2.5 Aac 14 Aac
Model Select
X
Vented Vented or Sealed