OutBackPower FXR Renewable Series 230V E Model Operator’s Manual

Specifications
900-0169-01-00 Rev B 73
Table 22 FXR Settings for 12-Volt Models
Field Item Default Minimum Maximum
Battery Equalize
Equalize Voltage
14.6 Vdc 11.0 Vdc 17.0 Vdc
(Equalize) Time
1.0 hours 0.0 hours 24.0 hours
Auxiliary Output
Aux Control Auto Off, Auto or On
Aux Mode Vent Fan
Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,
DC Divert, GT Limits, Source Status, AC Divert
(Load Shed) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(Load Shed ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Load Shed) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(Load Shed OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) ON: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(Gen Alert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Gen Alert) OFF: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(Vent Fan) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(Vent Fan) Off Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(DC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(DC Divert) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(DC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) ON: Batt >
14.0 Vdc 10.0 Vdc 18.0 Vdc
(AC Divert ON) Delay
0.5 minutes 0.1 minutes 25.0 minutes
(AC Divert) OFF: Batt <
11.0 Vdc 10.0 Vdc 18.0 Vdc
(AC Divert OFF) Delay
0.5 minutes 0.1 minutes 25.0 minutes
Inverter Stacking
Stack Mode Master Master, Slave, B Phase Master, C Phase Master
Power Save
Ranking
Mode = Master: Master Power Save Level
0 0 10
Mode = Slave: Slave Power Save Level
1 1 10
Grid-Tie Sell
Offset Enable Y Y or N
Sell Voltage
13.0 Vdc 11.0 Vdc 16.0 Vdc
Calibrate
AC Input Voltage
X
0 Vac –7 Vac 7 Vac
AC Output Voltage X
0 Vac –7 Vac 7 Vac
Battery Voltage
X
0.0 Vdc –0.2 Vdc 0.2 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency
X
50 Hz 50 Hz, 60 Hz
Stage 1 Voltage Trip
13
Over Voltage Clearance Time
X
1.5 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip
X
252 Vac 240 Vac 300 Vac
Under Voltage Clearance Time
X
2.0 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip
X
208 Vac 160 Vac 240 Vac
Stage 2 Voltage Trip
13
Over Voltage Clearance Time
X
0.2 seconds 0.12 seconds 4.0 seconds
Over Voltage Trip
X
264 Vac 240 Vac 300 Vac
Under Voltage Clearance Time
X
0.16 seconds 0.12 seconds 4.0 seconds
Under Voltage Trip
X
196 Vac 160 Vac 240 vac
Frequency Trip
13
Over Frequency Clearance Time X
0.16 seconds 0.12 seconds 5.0 seconds
Over
Frequency Trip
60-Hz system
X
60.5 Hz 60.1 Hz 65.0 Hz
50-Hz system 50.5 Hz 50.1 Hz 55.0 Hz
Under Frequency Clearance Time
X
0.16 seconds 0.12 seconds 5.0 seconds
Under
Frequency Trip
60-Hz system
X
59.3 Hz 55.0 Hz 59.9 Hz
50-Hz system 49.3 Hz 45.0 Hz 49.9 Hz
Mains Loss
13
Clearance Time
X
2.0 seconds 1.0 seconds 25.0 seconds
Reconnect Delay
X
60 seconds 2 seconds 302 seconds
Multi-Phase Coordination
Coordin. AC Connect/Disconn.
N Y or N
Sell Current Limit
Maximum Sell Current
This selection inoperative in 12-volt models
Model Select
X
Vented Vented or Sealed
13
The grid-interactive function is not available in 12-volt models. Adjusting these items will not affect operation.