OutBackPower FXR Renewable Series 230V E Model Operator’s Manual
900-0169-01-00 Rev B  53 
Troubleshooting 
Basic Troubleshooting 
Table 7 is organized in order of common symptoms, with a series of possible causes. Each cause also 
shows possible troubleshooting remedies, including system display checks where appropriate. 
These instructions are for use by qualified personnel who meet all local and governmental code 
requirements for licensing and training for the installation of electrical power systems with AC and DC 
voltage up to 600 volts. 
Figure 19  AC Test Points 
WARNING: Shock Hazard
During an error shutdown, the inverter’s output terminals are not live. However, 
if the inverter recovers from a shutdown, the terminals will become live without 
notice. Several error shutdowns can be recovered automatically, including 
Low 
Battery V
, 
High Battery V
, and 
Over Temperature
. See page 58. 
Table 7  Troubleshooting  
Symptom  Possible Cause  Possible Remedy
No AC output 
(will not invert). 
No DC voltage. 
Use a DC voltmeter to check the voltage directly on the DC 
terminals. If not present, the problem is external. If present, the 
inverter could be damaged. Contact OutBack Technical Support.
5
Inverter ON/OFF jumper 
missing. 
See the Installation Manual for the location of the jumper. Confirm 
the jumper is present. If missing, replace the jumper. Or follow the 
Installation Manual instructions to install an external switch.
Unit defaulted of
f
(No MATE3 present; initial 
install; Inverter ON/OFF jumper 
confirmed present). 
T
he FXR inverter is given an initial Off command in the factory. 
With DC present, use narrow pliers to remove the jumper from its 
pins. Once removed, install it again. This is the equivalent of 
“jiggling the switch.” 
Inverter set to 
Off
. 
MATE3 system display only: Set to 
On
with the 
INVERTER
hot key.
NOTE
: The ON/OFF jumper must be installed. 
Inverter set to 
Search
 (Search 
mode). 
MATE3 system display only: If constant power is required, set to 
On
with the 
INVERTER
hot key. (If this setting was intentional, then 
no action is required.)
5
 See inside front cover of this manual. 
In troubleshooting, 
AC voltages can be 
measured at the 
attachment screw for 
each AC conductor.