Outback Power FX and VFX Series Programming Manual
34
The default value for the power save level slave 
adjust only screen is 1. Press or to 
adjust this value. Press to change the 
value of each Slave FX.
The Slave(s) must be connected to Port 2 or 
higher on the HUB.
 With the Master FX default value of zero in the 
power save level master adjust only screen, all of 
the Slave FX’s will remain OFF until the Master 
FX needs help and calls for the Slave FX’s with 
a Slave ranking equal to 1 to come ON.
Choose a di erent Slave ranking for each Slave 
FX. This helps assure proper operation and allows 
them to come ON one at a time saving power in 
the long run. Otherwise, with a default value of 1 
for all Slaves, they will all come on whenever a 12 
amp load calls for more power, but then can 
quickly shut o  because multiple FXs provide far 
more than the required 12 amps. Ranking them 
1, 2, 3, 4 etc. means they will come on one at time
as needed to better serve the loads and conserve  
energy.
ADV/FX/STACK-----------P02
power save level 1
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK-----------------
 stacking setup
 completed
 TOP ADV MAIN
Press to return to the Main Menu.
Press to view the  nal stacking screen.
INC
DEC
DOWN
MAIN
PORT