Outback Power FX and VFX Series Programming Manual
33
Introduction to Power Save Levels 
Depending on the model, each FX consumes 20-25 watts of power when it remains on, even if it isn’t actively 
inverting or charging. OutBack Power Systems o ers the option to shut down (put into Silent mode) some or all 
of the Slave FXs until the loads require them to come on again.
• When a load exceeds 12 amps AC, the Master FX shares the load with one or more Slave FXs. 
• When the Master detects only a four amp load, a Slave FX goes into Silent mode; Slaves will continue to go into 
Silent mode as long as the Master detects four amps.
The next two screens in the MATE’s Stack menu adjust the power levels of the Master and Slave FXs. From any 
STACK PHASE screen:
•  Press once to bring up the power save level master adjust only screen
•  Press again to bring up the power save level slave adjust only screen
NOTE: These power save level master adjust only and power save level slave adjust only screens pertain to 
systems that have OB Slave L1 and/or OB Slave L2 type Slaves only.
ADV/FX/STACK-------------P01
(ANY SCREEN IN STACK PHASE)
DOWN INC DEC PORT
Press the soft key once.
ADV/FX/STACK------------P01
power save level 
master adjust only
DOWN INC DEC PORT
Press to increase the power save level 
master adjust only value. Any Slave with this value 
or lower which is assigned in the power save 
level slave adjust only screen (next), will be on 
with the Master. If the power save level master 
adjust only is three, for instance, any Slave 
assigned a value of 3 or lower will be on when 
the Master is on. Since the Master is essentially 
always ON, these Slaves will always be on as well. 
Any Slave with a value of 4 and higher will be 
Silent until the Master activates them for larger 
loads. For days of the week with small load 
demands, a user can decrease the power save 
level master adjust only value so fewer FXs are 
running. 
The default value is zero (only the Master is on). 
Press to view the power save level slave 
adjust only screen.