Installation Manual Instruction Manual

26
PARALLELED QUAD FX SYSTEM
All AC wiring from the AC source and to the AC loads must collectively handle 100 amps AC or more.
All other AC wiring must handle a capacity of 30 amps AC.
This system can continuously power 8-12kW of loads depending on which model is used.
Connecting more load than the continuous rating of the FX may cause breakers to trip or the FX to
shut o its AC output.
NOTES: Program the lowest-installed FX as Master (1-2ph MASTER) and the three remaining FXs as
OutBack L1 Slaves (OB SLAVE L1). The Master FX must be plugged into Port 1 of the HUB.
3-PHASE FX SYSTEM
This system produces 230VAC per phase and 400VAC from phase to phase. There can only be one
FX per phase on a 3-phase system for a maximum of three FXs total.
The AC wiring from the AC source and to the AC loads must handle 30 amps AC.
• All AC wiring must handle a capacity of 30 amps AC.
This system can power continuously up to 6-9kW of loads depending on which model is used.
• Connecting more load than the continuous rating of the FX may cause breakers to trip or the FX to
shut o its AC output.
The jumper in the HUB must be moved for 3-phase con guration (please see the HUB Installation
and User Guide). The Master FX must be plugged into Port 1 of the HUB.
NOTE:
Program the bottom FX as Master (3ph MASTER) and the upper two FXs as 3-phase Slaves
(3ph SLAVE). Keep the phases in order: phase one is connected to the FX programmed L1; phase
two is connected to L2; and phase three to L3 (or phases A, B, and C to inverters A, B, and C) as
shown in the diagram on the following page.