Installation Manual Instruction Manual

20
AC WIRING NOTES
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND/PE
CHASSIS GROUND/PE
AC NEUTRAL IN
AC HOT IN
BATTERY
FULL
OK
LOW
STATUS
INVERTER
AC IN
ERROR
BATTERY TEMP
MATE/HUB
INVERTER ON/OFF
INVERTER
ON/OFF
AUX+
AUX-
XCT-
XCT+
AC HOT (PHASE) OUT
Supplies the AC hot output conductors
through a 30 amp maximum AC branch
rated circuit breaker using 6 AWG (16.0 mm
2
)
wire and connect to the AC
AC NEUTRAL OUT/AC NEUTRAL IN
Connects the AC neutral input conductor to
the AC NEUTRAL IN terminal.
Connects the AC neutral output conductor
to the AC NEUTRAL OUT terminal.
AC HOT (PHASE) IN
The AC hot input conductor (brown) must
be supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.
6 AWG (16.0 mm
2
) wire is required for the
FX’s AC transfer relay.