Owners Manual Owner's manual
Operation
900-0117-01-00 Rev C 59
From the
CHARGER
hot key’s
Charger Status
screen, the
<Charger Mode>
soft key brings up a screen
that can turn on or turn off the charger. (See the inverter Operator’s Manual for a description of specific
charger functions.)
Figure 58 Using the CHARGER Hot Key (Charger Mode)
Soft Key Options:
<On> activates the charger for a cycle
consisting of bulk, absorption, and float
stages. Upon completion, the charger
remains in the float stage to maintain
the batteries until the AC input is
disconnected.
NOTE: This option varies with model.
In FX-class non-grid-interactive models,
the option operates as above.
In FX-class grid-interactive inverters, this
option is automatically selected when
the
Input Type
menu is set to
Gen
(see page 83). The <On> option cannot
be selected if the menu is set to
Grid
. In
these inverters, the
Charger Mode
menu can still enable or disable the
charger, but it cannot select the cycle.
In Radian-class inverters, this option
performs as above except when using
certain AC input modes with other
priorities. (See the <Auto> option and
the inverter Operator’s Manual.)
When <Auto> is selected, the
screen will display:
<Auto> activates the charger for a cycle
consisting of bulk, absorption, and float
stages. Upon completion, the charger
goes into Silent mode until it reaches
the “re-float” voltage. Then it will
re-enter the float stage.
NOTE:
T
his option varies with model. In
FX-class non-grid-interactive models,
the option operates as above.
In FX-class grid-interactive inverters, this
option is automatically selected when
the
Input Type
menu is set to
Grid
(see
page 83). The <Auto> option cannot be
selected if the menu is set to
Gen
. In
these inverters, the
Charger Mode
menu can still activate or deactivate the
charger, but it cannot select the cycle.
This option is not available on this
screen in Radian-class inverters; the
function operates automatically when
certain AC input modes are selected.
(See the inverter Operator’s Manual.)
<Off> disables the charger in
all inverter models.
When <On> is selected, the screen
will display:
When <Off> is selected, the screen
will display:
Screen Items: