Owners Manual Owner's manual

Configuration Wizard
900-0117-01-00 Rev C 133
Figure 164 Modifying an Existing Configuration
Soft Keys:
<Back> moves back one screen.
<Continue> moves forward to the next screen.
Set Points:
System Type (see page 74):
System Type
System Voltage
Array Wattage
Battery Type/Capacity
Battery Charging (see pages 89 and 89):
Absorb Voltage/Time
Float Voltage/Time
Equalize Voltage/Time
Re-Float Voltage
AC Configuration (See pages 83 - 87, and 100):
AC Output Voltage
(Vac)
AC Phase
AC Input Breaker Size
(amps)
Maximum Output Load
(amps)
Generator Configuration (See pages 74 and 115):
Generator Installed
– Y or N
Generator Type
AC
or
DC
Size
0.0
to
150.0
Generator Start
(manual, auto)
Aux Output Device Port
– 1
Control
(Radian only; AUX Relay or AUX Output)
Continued on next page...
To modify an existing configuration:
1. Access the
Main Menu
as shown in Figure 71.
2. Select the
Configuration Wizard
menu.
3. Select
Existing Configuration
.
4. Select <Continue>. This will bring up the four
Configuration Wizard
programming screens.
5. Use the control wheel to adjust the settings in each
screen where required. Record the settings on the
form provided in Table 11.