OutBack Power Installation and User Manual
78
DC Genset
Inthisscreen,YESmeansaDCgeneratoris
presentandtheAGSroutine,whichnormally
stopsthegeneratorupontheFXgoingtoFloator
Silent, will instead stop the generator when the 
vdc genstop setting is reached. 
isvoltagesettingwillterminateaVoltageStart
command when the battery voltage remains above 
itfor15minutesregardlessoftheDCGenset
setting. e setting can be adjusted using the 
<INC> and <DEC> so keys. Press the <DOWN> 
sokeytoviewtheAGSfaulttimescreen.
AGSFaultTimeistheperiodthegeneratoris
giventoconnecttotheFXsystemaertheAUX
outputhasbeenactivated.Ifthegeneratorfails
to connect and provide AC current, the MATE 
displaysanAGSerror.eusercansetthistime
anywherefrom5-30minutesbypressingthe
<INC> and <DEC> so keys. Press the <DOWN> 
so key to reach the cool down time screen.
ADV/MATE/AGS/SETUP
dc genset NO
 DOWN UP NO YES
NOTE:IfyouhaveageneratorthatproducesAC
voltage,maintaintheNOstatusshownonthis
screen.
ADV/MATE/AGS/SETUP-----
AGS fault time 17
 minutes
 DOWN UP INC DEC
VDC Genstop
ADV/MATE/AGS/SETUP-----
vdc genstop: 38.0 vdc
 DOWN UP INC DEC
NOTE:evdc genstop will turn o a generator 
even if the dc genset on the previous screen says 
<NO>.
Press the <DOWN> so key to go to the vdc 
genstop screen.