- Outback Power Hub User's Manual
7
HUB Operation
When the  rst powered OutBack product plugs into the HUB:
•  The HUB will go through a power up sequence that  ashes all of its LEDs. 
•  The POWER LED will remain on any time that one or more powered OutBack products are 
connected. 
•  After the MATE is connected it will start communicating with all connected devices. 
•  Each Port has an LED associated with it that is visible through the cover. 
•  Any device that is plugged in should have a  ickering LED when the MATE is 
  communicating with it. 
Note: In order to operate correctly, the HUB requires that the MATE be code version 2.0 or higher. (See 
“Checking the MATE Version” in the Troubleshooting section and/or see the MATE User Manual for 
more information.)
  10 9 8 7 6 5 4 3 2 1  2nd 1st
                   MATE MATE               
•  With the HUB mounted, plug in the FX Inverter/Chargers starting with Port 1.
•  Port 1’s FX is the Master FX in a multiple FX system.
•  When all the FXs are connected to the HUB, connect the Charge Controllers in any 
order.
•  After all devices are connected to the HUB, the MATE is always plugged in last using 
the 1st MATE port.
•  The 2nd MATE is inactive and should not be used.
•  Connections can be made with FXs or OutBack Charge Controllers already powered 
up or simply power up all devices when the connections to the HUB are complete.
•  After the devices are powered, the MATE will power up when it is connected; it will 
display a greeting and software revision information (see page 11)
•  FX AC input breakers and AC output breakers should be open until stacking pro-
gramming is complete.
•  To operate, the HUB requires at least one FX or Charge/Controller to be plugged in.
•  The MATE must be repolled to recognize any devices connected after it’s activated 
(see page 12)
The Master FX plugs into Port 1
Connecting to the HUB
HUB Ports (HUB 10)
2nd MATE 
Port is not 
used