12 VDC System DEFAULT MINIMUM MAXIMUM
Float Voltage 13.6 VDC 12 VDC 15 VDC
Absorb Voltage 14.4 VDC 13 VDC 16 VDC
EQ Voltage 14.6 VDC 14 VDC 17 VDC
ReFloat 12.5 VDC 12 VDC 13 VDC
LBCO 10.5 VDC 9 VDC 12 VDC
LBCI 12.5 VDC 10 VDC 14 VDC
Sell RE 13 VDC 10 VDC 15 VDC
Gen Alert
O Set Point 14 VDC 12 VDC 18 VDC
On Set Point 11 VDC 10 VDC 14 VDC
Load Shed O Set Point 11 VDC 10 VDC 14 VDC
Vent Fan ON Set Point 13 VDC 10 VDC 16 VDC
Diversion ON Set Point 14.6 VDC 12 VDC 16 VDC
Absorb Time 1.0 hours 0.0 hours 24.0 hours
EQ Time 1.0 hours 0.0 hours 24.0 hours
Float Time 1.0 hours 0.0 hours 24.0 hours
AC2/Gen Transfer Delay
(Cycles for AC)
10 cycles 0 cycles 240 cycles
Search 6 0 50
Grid Lower Limit 114 VAC 100 VAC 120 VAC
Grid Upper Limit 140 VAC 130 VAC 140 VAC
Charger OFF/AUTO/ON AUTO
AUX Output Option COOL FAN
Gen Alert ON Delay 4 min 0 min 240 min
Gen Alert OFF Delay 9 min 0 min 240 min
Vent Fan OFF Delay 5 min 0 min 30 min
Gen Window Lower Limit 114 VAC 100 VAC 120 VAC
Gen Upper Window Limit 140 VAC 130 VAC 150 VAC
AC1/Grid Transfer Delay 10 Cycles of AC 0 Cycles of AC 240 Cycles of AC
Set AUX Control AUTO
Search Pulses 8 2 20
Search Pulse Spacing 60 Cycles AC 4 Cycles AC 120 Cycles AC
Stacking Phase Master
InPut Select Grid
Charge Rates
Vented 24 & 48 VDC 18 AAC 0 AAC 20 AAC
Sealed 24 & 48 VDC 14 AAC 0 AAC 16 AAC
Grid Input Settings
Set AC Input Size
Grid-Tie 50 Amps 5 Amps 60 Amps
Gen Input Settings
Grid-Tie 30 Amps 5 Amps 60 Amps
FX Default Values (subject to change with FX upgrades)
CorrectionFactor•24VDC:Multiply12VDCvaluesby2•48VDC:Multiply12VDCvaluesby4