72
MULTIPLE AC SOURCES WITH THE FX INVERTER
When a system has the option of using either a generator or the utility grid as their AC input:
• BoththeAC“HotandAC“Neutral”linesmustbeconnectedtotheappropriatesource.
• Aconnectioncanbemadeusingasingle-pole,double-throwswitch(availablefromelectrical
component suppliers) which has one connection each for AC hot wire.
•ThisswitchmustberatedtohandlethesystemsmaximumACvoltageandACcurrent.
•Theswitchmustisolatethetwoinputsourcesfromeachother.Whentheswitchisthrown,theAC
connection to one line must be broken before contacting the other connection. (A common term
for this type of switch is break-before-make.
•Theneutrallinesarecommonthroughoutthesystem.Thesameappliestothegroundwires.
•Theelectricalsystemshouldhaveneutralandgroundbondedtogetheratasinglepoint.This
is shown in the lower right corner of the drawing for convenience, but the bonding is usually
performed in the main electrical panel.
•Ifanyotherneutral-groundbondsarepresentinthesystem,particularlyinthegenerator,theymust
be removed.
GRID
GEN
H N G
H N G
FX Inverter
H
N
G
H
N
G
Single-Pole
Double-Throw
Switch
L
O
A
D
S