3-PHASE FX SYSTEM
•Thissystemproduces120VACperphaseand208VACfromphasetophase.TherecanonlybeoneFXper
phase on a 3-phase system.
•AllFXACwiringmustbesizedtohandle60ampsACormore.
•Thissystemcanpowercontinuouslyupto10.8kWofloadsdependingonwhichmodelisused.
•ConnectingmorepowerthanthecontinuousratingoftheFXmaycausebreakerstotriportheFXtoshutoits
AC output.
•ThejumperintheHUBmustbeleftinthestandardposition(usuallycalledthe“series/parallel”position)for
3-phase conguration with LA Series grid-tied models. (This instruction is specic for these models, and may
conict with the HUB Installation and User Guide).
NOTE: Program the bottom FX as Master and the two upper FXs as 3-phase Slaves (3p Classic
B and 3p Classic C). Keep the phases in order: phase one is connected to the FX programmed
Master; phase two is connected to 3p Classic B; and phase three to 3p Classic C).