Installation Manual Owner manual

66
INSTALLATION TYPES
SINGLE FX SYSTEM
• AllFXACwiringmustbesizedtohandle60ampsACormore.
• A60AinputbreakermustbeusedforallFXmodels.
• AsingleFXcancontinuouslypower2.0kWto3.6kWofloadsdependingonwhichmodelisused.
• TheoutputofasingleFXcanbesteppedupto240VACwiththeFX-X240transformer.
GROUND TBB
MECHANICAL
INTERLOCK
INVERTER/CHARGER
AC HOT IN AC HOT OUT
HUB/MATE
60 AMP
BYPASS
BREAKER
30 AMP
OUTPUT
BREAKER
AC NEUTRAL OUT
CHASSIS GROUND
DISPLAY
60 AMP
INPUT
BREAKER
BLACK
BLACK
BLACK
WHITE
GREEN
NOTE:
1. All cables are to be
6AWG THHN or larger.
AC SOURCE
AC LOADS
WHITE
WHITE
AC NEUTRAL IN
WHITE
BLACK
BLACKBLACK
BLACK