Installation Manual Owner manual
62
AC WIRING NOTES
AC HOT OUT
• AChotoutputconductor(black)wire
gauge must be sized to the breakers and
loads.
AC NEUTRAL OUT/AC NEUTRAL IN
•Bothneutralterminalsarecommonwith
each other within the FX.
•Onlyoneneutralneedstoconnectatthe
terminal if a separate common neutral bus
bar is installed.
CHASSIS GROUND
• BothCHASSISGROUNDterminalsare
common within the FX.
•TheACinputandACoutputground
wires can connect to these terminals, or
one ground wire can be connected if a
common ground bus bar is installed.
AC HOT IN
• TheAChotinputconductor(black)must
be supplied through a 60 amp maximum
AC branch rated circuit breaker.
• 6AWG(0.184”or4.11mm)wireis
recommended for the FX’s AC transfer
relay.