AC AND DC GROUNDING REQUIREMENTS
• Connectonlytoagrounded,permanentwiringsystem.Ensurethereisonlyoneneutral-ground
connection in the system at any time. Some codes require this connection be made at the main
panel only.
• Somegeneratorshavetheirownneutral-groundconnection.Ifageneratorisused,itsneutral-
ground connection will need to be disengaged for proper system operation.
• Forallinstallations,thenegativebatteryconductorshouldbebondedtothegroundingsystemat
one (and only one) point in the system.
• OutBackproductsarenotdesignedforuseinapositivegroundedsystem.PleasecontactOutBack
Technical Support for further information.
The equipment ground on each is marked with this symbol:
Box lug for grounding the FX chassis