OutBack Power GSLC Installation Manual
Wiring 
900-0123-01-00 Rev C  43 
In Figure 39, when Switch 1 is on (normal operation), the inverter’s output sends power to the loads. 
Switch 2 is off, preventing the inverter from sending power back to the AC source (backfeeding). 
When Switch 2 is on (bypass operation), the AC source sends power directly to the loads. Switch 1 is 
off, removing the inverter’s output from the loads. This also prevents the AC source from backfeeding 
the inverter. With the inverter removed from the circuit, maintenance can be performed as necessary. 
Figure 39  Bypass Switches 
The GSLC can be ordered with bypass circuit breakers for this purpose, or it has a bypass option (the 
GS-IOB-120/240VAC or GS-IOB-230VAC) which can be installed.  
Figure 40  OutBack Bypass (split-phase) 
IMPORTANT:  
If multiple Radian inverters are stacked in a single system, then these devices 
cannot be used. The bypass function must be simultaneous for all inverters. The 
GSLC bypass kits operate independently, not simultaneously.
In a new system with multiple Radian inverters, the basic GSLC should be used in conjunction with an 
external assembly of this kind, as shown in Figure 41. The GS-IOB kits should not be installed, or if 
previously installed, should be removed and all wires disconnected. 
OutBack does not offer a solution for bypassing multiple inverters. However, electrical suppliers offer 
both manual and automatic double-pole, double-throw bypass switches in a range of sizes and 
options. These are highly recommended for systems larger than a single inverter.  
WARNING: Shock Hazard or Equipment Damage 
Using independent bypass devices on multiple inverters can result in power being routed 
to inappropriate places. This could lead to an electric shock or to equipment damage. 
AC Loads 
Switch 1 
Switch 2 
Inverter Output 
Bypass AC Source 
Switch 1 and Switch 2 are prevented 
from being on at the same time by the 
Mechanical Interlock. Although both 
switches can be off, only one can be on. 
In OutBack bypass assemblies, circuit 
breakers are used instead of standard 
switches. 
The inverter may use an AC 
source which powers the 
inverter’s output. The bypass 
assembly does not disconnect 
the inverter’s input. 
AC Source 
AC Loads 
GSLC Bypass 
Disconnected 
Radian 
Inverter 
Input Wiring 
Output Wiring 