OutBack Power GSLC Installation Manual
Wiring 
900-0123-01-00 Rev C  37 
AC Wiring  
WARNING: Shock Hazard 
Ensure all circuit breakers or disconnect devices are turned off or disconnected before 
wiring. Make certain the inverter and other active devices are turned off or disabled 
before wiring. 
Split-Phase Wiring 
The GSLC can have multiple terminal bus bars for multiple AC connections. Because the Radian 
inverter possesses two sets of AC input connections and one set of output connections, up to three 
TBB sets are available. Each set of bus bars are paired in red and black, for the 120/240 Vac 
connections required by the Radian inverter. 
The TBB set on the left is generally used for the inverter’s AC output connections. The central TBB set 
is for utility grid connections and the right TBB set is for a generator. The preassembled GSLC models 
follow this convention. 
Each TBB accepts conductors from 1/0 (70 mm
2
) to #14 AWG (2.5 mm
2
). See Table 2 on page 29 for 
required torque values. 
If steps are inappropriate for a given system (such as instructions for a generator when none is 
present), they can be ignored. 
Figure 33    AC Terminal Bus Bars (split-phase) 
AC Output 
Grid 
Generator 
Neutral 
To make the external AC connections to the 
split-phase GSLC:  
1.  Connect the L1 wire from the AC load panel 
to black TBB 1 (AC OUT - HOT LEG 1). 
Connect the L2 wire from the AC load panel 
to red TBB 2 (AC OUT - HOT LEG 2). 
2.  Connect the neutral wire from the AC load 
panel to neutral TBB 
3. 
3.  Connect the L1 wire from the utility grid 
panel (if present) to black TBB 
4 
(GRID IN - HOT LEG 1). Connect the L2 wire 
from the utility grid panel to red TBB 5
(GRID IN - HOT LEG 2). 
4.  Connect the neutral wire from the utility 
grid panel (if present) to neutral TBB 3. 
5.  Connect the L1 wire from the generator  
(if present) to black TBB 
6 (GEN IN - HOT  
LEG 1). Connect the L2 wire from the 
generator to red TBB 
7
(GEN IN - HOT LEG 2). 
6.  Connect the neutral wire from the generator 
(if present) to neutral TBB 
3. 
NOTE: Remove the neutral-ground bond if 
necessary. See page 30.  
1 
2 
3 
4 
5 
6 
7 