Bonding 
All GSLC models are equipped with a mechanical bond between AC 
neutral
 and ground.  
All models that do not include the GFDI are also equipped with a mechanical bond between DC 
negative
 and ground. These can be useful in stand-alone systems where no other bond is provided. 
If other bonds are present, or if the GFDI is installed later, the GSLC bonds need to be removed. 
WARNING: Shock Hazard 
If the GFDI is manually installed (see page 24 and the GFDI manual), the negative-ground 
bond on the GSLC must be removed. This must also be done if any other PV ground-fault 
device is present that establishes its own negative-ground bond. GSLC models purchased 
with the OutBack GFDI do not have a bond between negative and ground.  
`  
Figure 27  Removing Bonding Connections 
The GSLC’s neutral bus bar is located in 
the lower right portion of the GSLC.  
The neutral-ground bond is established 
at one end of the bar, near the base of 
the GSLC.  
To remove either of the bond connections:  
1.  Using a Phillips screwdriver, remove the screw 
shown above.  
2.  Remove the metal standoff beneath the bus 
bar. The screw and bus bar provide the 
mechanical bond to the chassis ground. 
3.  Rotate the TBB mount. Insert the bus bar into 
the open end of the TBB mount so that the TBB 
mount supports the bus bar. It may be 
necessary to loosen the TBB mount screw 
before rotating it. 
4.  Retighten the screw to secure the TBB mount. 
The GSLC’s negative (–) bus bar is located 
near the top of the GSLC. It is attached to 
the inverter negative (–) bus and its shunt. 
NOTES: 
 If the TBB is connected directly to  
the enclosure by a screw, then the 
bond is connected. 
If the TBB is held by the TBB mount 
and the TBB mount is secured to the 
enclosure, the bond is disconnected. 
 The installed Neutral TBB has white 
insulators. A second Neutral TBB with 
blue insulators is included in the kit 
for locations where blue is standard. 
Screw 
TBB 
Mount 
TBB 
Mount 
Neutral-Ground Bond 
Negative-Ground Bond 
Bottom of GSLC 
Standoff 
Standoff 
Inverter 
Negative (
–) 
Bus Bar
Top of GSLC 
Screw 