Single-Phase Wiring 
The GSLC allows multiple terminal bus bars (TBB) for multiple AC connections. Because the Radian 
inverter possesses two sets of AC input connections and one set of output connections, three terminal 
bus bars are available for hot connections, as well as one neutral bus bar. The hot bus bars use brown 
insulators in 230 Vac models. The neutral bus bar uses blue insulators in 230 vac models. 
The TBB on the left is generally used for the inverter’s AC output connections. The central TBB is for 
utility grid connections and the right TBB is for a generator. The preassembled GSLC models follow 
this convention. 
Each TBB accepts conductors from 70 mm
2
 (1/0 AWG) to 2.5 mm
2
 (#14 AWG). See Table 2 on page 29 
for required torque values. 
If steps are inappropriate for a given system (such as instructions for a generator when none is 
present), they can be ignored. 
Figure 35  AC Terminal Bus Bars (single-phase) 
AC Output 
Grid 
Generator 
Neutral 
To make external AC connections to the 
single-phase GSLC:  
1. Connect the hot wire from the AC load 
panel to brown TBB 1 (AC Output).  
2. Connect the neutral wire from the AC 
load panel to neutral TBB 
2. 
3. Connect the hot wire from the utility grid 
panel (if present) to brown TBB 3 (Grid).  
4. Connect the neutral wire from the utility 
grid panel (if present) to neutral TBB 2. 
5. Connect the hot wire from the generator 
(if present) to brown TBB 4 (Generator).  
6. Connect the neutral wire from the 
generator (if present) to neutral TBB 2. 
NOTE: Remove the neutral-ground bond  
if necessary.  See page 30.   
The neutral insulator in Figure 35 is in the 
position which opens the bond. 