OutBack Power Installation Manual
Installation 
38  900-0123-01-00 Rev C 
Bypass Assembly 
Bypass switching can be used when the inverter is shut down for maintenance. This topic is discussed 
more beginning on page 42. The GSLC can be equipped with the GS-IOB-120/240VAC bypass 
assembly. The instructions on this page are for making external connections to the bypass assembly 
after installation. (The installation wiring for the GS-IOB-120/240VAC is described on page 41.) 
If no bypass assembly is used, connections should be made directly to each TBB from the circuit 
breakers for the inverter, AC sources, and loads. These connections are designated in Figure 33. 
Wiring diagrams for an assembled 120/240 Vac system are shown beginning on page 45.
Figure 34  Inverter AC Connections (split-phase) 
To make the connections to the Radian inverter: 
1.  Designate the top AC circuit breaker as the 
inverter AC output disconnect. Install a wire from 
the black AC output TBB (as shown in Figure 33. to 
the disconnect marked by 
1. 
2.  Install a wire from the red AC output TBB to the 
disconnect marked by 
2. 
3.  Install wires on the left side of the disconnect as 
marked by 
3 and 4. Connect these wires to the 
appropriate L1 and L2 output terminals on  
the Radian inverter. 
4.  Designate the third AC circuit breaker from the 
top as the disconnect for one AC source (GRID or 
GEN). Install a wire from the black source circuit 
TBB (as shown in Figure 33) to the disconnect 
marked by 5. 
5.  Install a wire from the red source circuit TBB to  
the disconnect marked by 
6. 
6.  Install wires on the right side of the disconnect  
as marked by 
7 and 8. Connect these wires to the 
appropriate L1 and L2 input terminals on the 
Radian inverter (the terminals labeled either GRID 
or GEN). 
7.  If a second AC source is present, repeat steps 4 
through 6 using the bottom circuit breaker. 
8.  Install a wire on the inverter’s NEU terminal and 
connect it to the GSLC’s neutral TBB (as shown in 
Figure 33). Only one neutral connection is required. 
GRID
 and 
GEN
 inputs 
AC Output 
Disconnects 
8 
2 
3
4 
5 
6 
7 
1 