OutBack Power Installation Manual
Installation 
32  900-0123-01-00 Rev C 
Battery Negative (–) Cable 
The battery negative (–) cables connect to the pre-installed shunt. This shunt is located to the upper 
left of the main inverter disconnect. It is designed for several ring lugs to be bolted to it, with 
openings of 3/8" (10 mm) diameter. 
See item 
C
 in Figure 28 for an illustration of hardware installation order on the shunt. The shunt plate 
(GS-SBUS) may or may not be present. 
NOTE
: Do not install hardware in a different order from the illustrations in Figure 28. In all cases the 
battery cable lug must be the first item installed. It must make solid contact with the surface. 
Figure 28   Battery Connections 
Shunt 
Battery 
Cable Lug 
Flat Washer 
Lock Washer 
Shunt 
Battery 
Cable Lug 
DC Disconnect 
Flat Washer 
Lock 
Nut 
Charge Controller 
Ring Terminal
Battery 
Monitor Ring 
Shunt Plate  
(if present) 
3/8” Hex Bolt 
Hardware Connection  
to DC Disconnect 
Flat Washer 
Lock Washer 
M8 -1.25 Hex Bolt 
Flat 
Washer 
Nut 
Hardware Connection  
to DC Positive (+) Plate 
Hardware Connection  
to Shunt 
DC positive (+)  
cable plate (bus bar) 
Battery 
Cable Lug
A 
C
B