OutBack Power Installation Manual
Assembly 
900-0123-01-00 Rev C  21 
Installing Inverter Positive Bus Bars 
Figure 19  Inverter Bus Bars 
The GSLC parts kit contains two bus bars, 
A
 and 
B
, which attach 
to the tops of the DC disconnects. These bus bars make the 
connections with the Radian inverter’s positive DC terminals. 
Although they have similar shapes, the bus bars are not 
interchangeable. 
NOTE
: 
B 
is not included with model GSLC175PV1-120/240 or 
model GSLC175PV1-230. When these models are in use, begin 
the instructions with step 2. 
A 
B 
To assemble the Inverter Positive (+) Bus Bars: 
1.  Attach bus bar B to the top terminal of the 
DC disconnect on the right, using the stud and 
hardware on the back of the DC disconnect. 
Tighten the nuts to the values shown in  
Table 1 on page 19. 
B 
A 
Top Bar 
A 
2.  The GSLC’s hardware kit contains a top bar which attaches 
to bus bar A. Attach these two bars together using a 5/16" 
flat washer, a 5/16" lock washer, and an M8 nut (included in 
hardware kit). Tighten to the value shown in 
Table 1 on 
page 19. 
3.  Mount bus bar 
A
 and the top bar to the top 
terminal of the DC disconnect on the left.  
Tighten to the value shown in Table 1 on page 19. 