OutBack Power Installation Manual
Installation 
20  900-0123-01-00 Rev C 
Assembling DC Positive (+) Cable Plate (Bus Bar) 
NOTE
: These instructions are not used with model GSLCPV1-120/240 and models GSLC175PV1-230.  
If using either of these models, proceed to page 21 or the next appropriate instruction. 
Figure 18  Assembling the DC Positive (+) Cable Plate 
The bottom of each DC disconnect 
(circuit breaker) is bolted to a metal 
plate (bus bar) which receives the 
inverter’s positive (+) battery cables. 
To assemble the DC Positive Plate: 
1. Remove the nuts and other hardware 
(washer, lock washer, hex nut) from the 
bottom terminal in the back of each DC 
disconnect.  
2. Place the two DC disconnects side 
by side. 
3. Orient the DC positive plate so that the 
three largest holes are at the top. These 
holes have a diameter of 0.50" (1.3 cm). 
Insert the studs on each disconnect 
through the first and third holes. 
4. Replace the disconnect hardware 
(washer, lock washer, hex nut). Tighten 
the nuts to the values shown in Table 1 
on page 19. The plate will hold the two 