OutBack Power Installation Manual
Assembly 
900-0123-01-00 Rev C  19 
Remove Interior Cover 
In order to make any wiring connections or to install components, the interior cover must be removed 
to expose the interior of the enclosure. (This cover is sometimes called the “dead front.”) 
Figure 16  Removing the Interior Cover from the GSLC 
Installing the Internal Hardware 
Table 1  Size and Torque Requirements for Circuit Breakers and Bus Bars 
Item 
Terminal/Bolt Size 
Torque Requirements 
Inverter Positive (+) Bus Bars  M8  60 in-lb (6.8 Nm) 
Shunt Bolts  3/8"  60 in-lb (6.8 Nm) 
DC Positive (+) Cable Plate  Top Holes (x3)  60 in-lb (6.8 Nm) 
  Bottom Holes (x7)  50 in-lb (5.7 Nm) 
Circuit Breaker Studs  M8  20 in-lb (2.3 Nm) 
  1/4"  35 in-lb (4.0 Nm) 
  5/16"  50 in-lb (5.7 Nm) 
  3/8"  225 in-lb (25.5 Nm) 
Figure 17  DC Positive Cable Plate (FW-BBUS) 
To Remove the Interior Cover: 
1.  Remove the three screws along the top of the enclosure 
(with one star washer). 
2.  Remove the three screws along the bottom of the 
enclosure (with one star washer). 
3.  Lift the front cover off the enclosure. 
Remove (x3) 
Remove (x3) 
Interior 
Cover 
Top Holes 
Bottom Holes 
0.5" (12.7 mm) 
0.31" (8 mm) 
0.4" (10 mm) 
NOTE: The DC Positive (+) Cable 
Plate (FW-BBUS) is not included 
with model GSLC175PV1-120/240 
or model GSLC175PV1-230. It 
cannot be used with these models. 