OutBack Power GS4048A and GS8048A QuickStart Guide with GSLC
CAUTION: Equipment Damage
These procedures should be done by a qualified installer who is trained on programming inverter power systems. 
Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by 
inaccurate programming is not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not 
communicate or operate correctly unless their firmware is above a specified revision number.
For models GS8048A and GS4048A, the firmware must be revision 001.005.xxx or higher.
The MATE3 must be revision 002.017.xxx or higher.
Quick Start Guide
900-0162-01-00 Rev A.vsd\Page-1\2014-01-24
©2014 OutBack Power Technologies. All Rights Reserved.
Setup and Programming
Contact Technical Support:
Telephone: +1.360.618.4363
Email:  Support@outbackpower.com
Website:  www.outbackpower.com
RADIAN Series
HUB 10.3
Communications 
Manager 
MATE3 
System 
Display and 
Controller
Radian Inverter/Charger
GS Load Center 
(GSLC)
FM80 Charge 
Controllers 
(x2) 
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 12 feet (3.7 m) of 
the equipment. This unit employs mechanical relays and is not ignition-
protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with 
this equipment.
IMPORTANT: 
Clearance and access requirements may vary by location. Maintaining a 36” 
(91.4 cm) clear space in front of the system for access is recommended. 
Consult local electric code to confirm clearance and access requirements 
for the specific location.
IMPORTANT: 
Not intended for use with 
life support equipment.
AC Source
Utility Grid or
AC Generator 
Main Electrical Panel (or overcurrent 
device for the AC source)
Electrical Distribution Subpanel 
(Load Panel)
Photovoltaic (PV) Array 
Battery Bank
Customer-Supplied Components
Inverter/Charger
GS Load Center
System Display 
and Controller
MATE3 depicted 
(with FW-MB3 
mounting bracket)
GS8048A
GS4048A
Radian System Products 
Major Components
Optional OutBack Components
FLEXnet DC Monitor (FN-DC)
Remote Temperature Sensor (RTS)
Charge Controller
FLEXmax 80 depicted 
(with FW-CCB2 
mounting bracket)
PV Combiner Box PV12 depicted
Communications 
Manager
HUB10.3 depicted
GSLC175-PV-120/240
GSLC175PV1-120/240
(both depicted)
EnergyCell depicted
Note:  See the MATE3 
manual for details on 
generator control.
The MATE3 Configuration 
Wizard allows quick setup of 
parameters that apply to all 
systems. The Configuration 
Wizard is reached from the 
MATE3 Main Menu as shown 
to the right.
The firmware revision of all 
devices can be confirmed by 
navigating from the MATE3 
Main Menu as shown below. 
Upgrades to the firmware 
revision can be downloaded 
from the OutBack website 
www.outbackpower.com.
S
Firmware Revision
Configuration Wizard
Off Grid
Grid Tied Backup
This advances the display to the 
Setup Complete screen.
C
C
C
S S S
C
This advances the display to the 
Setup Complete screen if the 
FLEXnet DC is not installed. If the 
FLEXnet DC is installed, the display 
advances to the Shunt screens.
If FN-DC is installed...
If FN-DC is installed...
If FN-DC is installed...
Generator Installed Y
Generator Type AC Size 5.0 kW 
Generator Start Manual
AUX Output Device Port 1
Back   Continue
New Configuration  >>
Existing Configuration >>
Restore Configuration  >> 
System Type Grid Tied 
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA  Capacity  500 Ah 
Back   Continue
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back   Continue
New Configuration Initialized
Back  Continue
Shunt A
Connection Inverter
Back   Continue
Shunt B
Connection Charge Controller
Back   Continue
Shunt C
Connection Charge Controller
Back   Continue
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00  
Back   Continue
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Back   Continue
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Back   Continue
Shunt A
Connection Inverter
Back   Continue
Shunt B
Connection  Charge Controller
Back   Continue
Shunt C
Connection  Charge Controller
Back   Continue
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back   Continue
Shunt B
Connection Charge Controller
Back   Continue
Shunt C
Connection Charge Controller
Back   Continue
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Back   Continue
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back   Continue
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00  
Back   Continue
Generator Installed  N
Generator Type AC Size 5.0 kW 
Generator Start  Manual
AUX Output Device Port 1
Back   Continue
AC Output Voltage 240 VAC 
AC Phase Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A 
Back   Continue
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Back   Continue
Generator Installed  N
Generator Type AC Size 5.0 kW 
Generator Start Manual
AUX Output Device Port 1
Back   Continue
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back   Continue
AC Output Voltage 240 VAC 
AC Phase  Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A
Back   Continue
System Type Backup 
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity  500 Ah 
Back   Continue
Shunt A
Connection Inverter  
Back   Continue
AC Output Voltage 240 VAC 
AC Phase  Single
AC Input Breaker Size 50 A
Maximum Output Load 33 A
Back   Continue
Absorb Voltage 57.6 VDC Time  1.0
Float Voltage 54.4 VDC Time  1.0
Equalize Voltage 60.0 VDC Time  3.0
Re-Float Voltage 44.0 VDC
Back   Continue
System Type Off Grid 
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA  Capacity 500 Ah 
Back    Continue
Settings   >>
Configuration Wizard >>
Device Data Logs  >>
Event Logs   >>
Firmware Update  >>
System  >>
Inverter   >>
Charge Controller  >>
Battery Monitor  >>
MATE3  >>
System
System Information  >>
Save / Store Information >>
Firmware Version  >>
Date and Time  >>
LCD Display  >>
MATE3 002.017.018
1: GS8048A 001.005.002
2: GS8048A 001.005.002 
Settings   >>
Configuration Wizard  >>
Device Data Logs >>
Event Logs  >>
Firmware Update  >>
Settings
Configuration Wizard
New Configuration 
!
Masters of the Off-Grid.™
First Choice for the New Grid.