Outback Power GS4048A and GS8048A Specification Sheet

2
OutBack Power Technologies, Inc. 1628 W Williams Drive, Phoenix, AZ 85027
Tel: +1 360 435 6030 Technical Support: +1 360 618 4363 Email: sales@outbackpower.com
For more information visit www.outbackpower.com
© 2020 OutBack Power Technologies, Inc. All Rights Reserved. Trademarks and logos are the property of Alpha Technologies Services, Inc.,
EnerSys and its affiliates unless otherwise noted. Subject to revisions without prior notice. E. & O.E.
Radian A-Series Specifications
Models:
GS8048A GS4048A
Instantaneous Power (100ms)
16970VA 8500VA
Surge Power (5 sec)
12000VA 6000VA
Peak Power (30 min)
9000VA 4500VA
Continuous Power Rating (@ 25°C)
8000VA 4000VA
Nominal DC Input Voltage
48VDC 48VDC
AC Output Voltage (Selectable)
120/240VAC (200 to 260VAC) 120/240VAC (200 to 260VAC)
AC Output Frequency (Selectable)
60Hz (50Hz) 60Hz (50Hz)
Continuous AC Output Current (@ 25°C)
33.3AAC @ 240VAC 16.7AAC
Idle Power
Invert mode, no load: 34W Search: 10W Invert mode, no load: 34W Search: 10W
Typical Efficiency
93% 93%
CEC Weighted Efficiency
92.5% 92.5%
Total Harmonic Distortion
Typical: <2% Maximum: <5% Typical: <2% Maximum: <5%
Output Voltage Regulation
±2% ±2%
AC Input Voltage Range (MATE3s Adjustable)
L1-N or L2-N: 85 to 140VAC L1-N or L2-N: 85 to 140VAC
AC Input Frequency Range
@ 60Hz: 54 to 66Hz @ 50Hz: 45 to 55Hz
Grid-Interactive Voltage Range
L1-N or L2-N: 85 to 140VAC L1-N or L2-N: 108 to 132VAC
Grid-Interactive Frequency Range
59.3 to 60.5Hz 59.3 to 60.5Hz
Maximum AC Input Current
50AAC @ 240VAC 50AAC @ 240VAC
Maximum Utility Interactive Current
30A 15A
Continuous Battery Charge Output
115ADC 57.5ADC
Advanced Battery Charging
Flooded, gel, AGM, lithium-ion and flow chemistry Flooded, gel, AGM, lithium-ion and flow chemistry
DC Input Voltage Range
40 to 64VDC 40 to 64VDC
Accessory Ports
Remote temperature sensor (included), MATE3s and HUB communications Remote temperature sensor (included), MATE3s and HUB communications
Warranty
Standard 5 year, extended 10 year available Standard 5 year, extended 10 year available
Weight (lb/kg)
Unit: 125 / 56.7 Shipping: 140 / 63.5 Unit: 82 / 37.2 Shipping: 94 / 42.6
Dimensions H × W × D (in/cm)
Unit: 28 × 16 × 8.7 / 71.1 × 40.6 × 22.1 Shipping: 34.5 × 21 × 14.5 / 87.6 × 53.3 × 36.8 Unit: 28 × 16 × 8.7 / 71.1 × 40.6 × 22.1 Shipping: 34.5 × 21 × 14.5 / 87.6 × 53.3 × 36.8
Temperature Range
Rated: –20 to 50°C Maximum: –40 to 60°C Rated: –20 to 50°C Maximum: –40 to 60°C
Listings/Certifications
ETL listed to UL 1741 SA, CE, CSA C22.2 No. 107.1, UL 778 Annex F, IEC 62109-1 ETL, RoHS compliant per directive
2011/65/EU, FCC Class B, IEEE 1574.1, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
ETL listed to UL 1741 SA, CE, CSA C22.2 No. 107.1, UL 778 Annex F, IEC 62109-1 ETL, RoHS compliant per directive
2011/65/EU, FCC Class B, IEEE 1574.1, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
Non-Volatile Memory
Yes Yes
Field Upgradeable Firmware
Yes Yes
Chassis Type
Vented Vented
Radian GS8048A Power Factor Chart
Power Factor
8.0kVA 8.0kW 8.0kVA
6.8kW
Power Rating Notes
Inverters that specify power in VA but do not use the unity standard Power Factor (PF)
could have misleading power specifications. Volt-amps (VA) is a total inverter output,
while watts (W) represent the power consumed by the electrical loads. PF, which varies
by types of loads, is the ratio of W to VA, and the difference between the two is power
in the circuit that does no useful work. At 1.0PF (unity), all power is used. This is the
industry standard used by OutBack Power.
1.0
0.75
0.5
0.25
0.0
Industry-Standard Non-Industry Standard
0.85
Radian GS8048A Power Rating Chart
Power (VA)
20000
15000
10000
5000
0
100ms 5 sec 30 min continuous
Instantaneous Power Rating
Most stringent, massive load start GS8048A: 16970VA
Surge Power Rating
Less stringent load start GS8048A: 12000VA
Peak Power Rating
Frequent “heavy duty” load requirements GS8048A: 9000VA
Continuous Power Rating
Sustained “real world” load requirements GS8048A: 8000VA
16970VA
12000VA
9000VA
8000VA
Radian GS8048A Efficiency Rating Chart
Efficiency
93% (TYPICAL)
Typical Efficiency Rating
Real world efficiency with variable loads GS8048A: 93%
CEC Efficiency Rating
Most stringent US rating GS8048A: 92.5%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
2kVA 4kVA 6kVA 8kVA
92.5%
(CEC)
INVERTING SELLING
06/2020
#980-00076-01-001 REV B