Installation Manual User guide

Assembly
900-0123-01-00 Rev C 19
Remove Interior Cover
In order to make any wiring connections or to install components, the interior cover must be removed
to expose the interior of the enclosure. (This cover is sometimes called the “dead front.”)
Figure 16 Removing the Interior Cover from the GSLC
Installing the Internal Hardware
Table 1 Size and Torque Requirements for Circuit Breakers and Bus Bars
Item
Terminal/Bolt Size
Torque Requirements
Inverter Positive (+) Bus Bars M8 60 in-lb (6.8 Nm)
Shunt Bolts 3/8" 60 in-lb (6.8 Nm)
DC Positive (+) Cable Plate Top Holes (x3) 60 in-lb (6.8 Nm)
Bottom Holes (x7) 50 in-lb (5.7 Nm)
Circuit Breaker Studs M8 20 in-lb (2.3 Nm)
1/4" 35 in-lb (4.0 Nm)
5/16" 50 in-lb (5.7 Nm)
3/8" 225 in-lb (25.5 Nm)
Figure 17 DC Positive Cable Plate (FW-BBUS)
To Remove the Interior Cover:
1. Remove the three screws along the top of the enclosure
(with one star washer).
2. Remove the three screws along the bottom of the
enclosure (with one star washer).
3. Lift the front cover off the enclosure.
Remove (x3)
Remove (x3)
Interior
Cover
Top Holes
Bottom Holes
0.5" (12.7 mm)
0.31" (8 mm)
0.4" (10 mm)
NOTE: The DC Positive (+) Cable
Plate (FW-BBUS) is not included
with model GSLC175PV1-120/240
or model GSLC175PV1-230. It
cannot be used with these models.