User Guide
Specifications 
52  900-0112-01-00 Rev B 
Table 22  48-Volt Inverter Settings (MATE3) 
Field Item Default Minimum Maximum 
Sensitivity (see page 14 for increments) 
6 0  50 
Pulse Length 
8 4  20 
Search 
Pulse Spacing 
60 AC cycles  4 AC cycles  120 AC cycles 
Input Type  Grid  Grid or Gen 
Input Support  Y  Y or N 
Grid Input AC Limit 
25 Aac  2.5 Aac  30 Aac 
Gen Input AC Limit 
25 Aac  2.5 Aac  30 Aac 
AC Input and 
Current Limit 
Charger AC Limit  
5.5 Aac  0 Aac  6 Aac 
AC1/Grid Lower Limit 
208 Vac  140 Vac  220 Vac 
AC1/Grid Upper Limit 
252 Vac  250 Vac  280 Vac 
Grid AC Input 
Voltage Limits 
AC1/Grid Transfer Delay 
6 AC cycles  0 AC cycles  240 AC cycles 
LowerVoltage Limit 
208 Vac  140 Vac  220 Vac 
Upper Voltage Limit 
252 Vac  250 Vac  280 Vac 
Transfer Delay 
60 AC cycles  0 AC cycles  240 AC cycles 
Gen AC Input 
Voltage Limits 
Connect Delay 
0.5 minutes  0.2 minutes  15 minutes 
AC Output 
AC Output 
230 Vac  210 Vac  250 Vac 
Cut-Out Voltage 
42 Vdc  36 Vdc  48 Vdc 
Low Battery 
Cut-In Voltage 
50 Vdc  40 Vdc  56 Vdc 
Absorb Voltage 
57.6 Vdc  52 Vdc  64 Vdc 
(Absorb) Time 
1.0 hours  0.0 hours  24.0 hours 
Float Voltage 
54.4 Vdc  48 Vdc  60 Vdc 
(Float) Time 
1.0 hours  0.0 hours  24.0 hours 
Battery Charger 
Re-Float Voltage 
50 Vdc  48 Vdc  26 Vdc 
Equalize Voltage 
58.4 Vdc  56 Vdc  68 Vdc 
Battery Equalize 
(Equalize) Time 
1.0 hours  0.0 hours  24.0 hours 
Aux Mode  Cool Fan 
Remote, Load Shed, Gen Alert, Fault, Vent Fan, 
Cool Fan, Divert DC, Divert AC, or AC Drop 
(Load Shed) Enable Voltage 
44 Vdc  40 Vdc  56 Vdc 
(Gen Alert) ON Voltage 
44 Vdc  40 Vdc  56 Vdc 
(Gen Alert ON) Delay 
4 minutes  0 minutes  240 minutes 
(Gen Alert) OFF Voltage 
56 Vdc  48 Vdc  72 Vdc 
(Gen Alert OFF) Delay 
9 minutes  0 minutes  240 minutes 
(Vent Fan) Enable Voltage 
52 Vdc  40 Vdc  64 Vdc 
(Vent Fan) Off Period 
5 minutes  0 minutes  30 minutes 
(Divert DC or AC) Enable Voltage 
58.4 Vdc  48 Vdc  64 Vdc 
Auxiliary 
Output 
(Divert DC or AC) Off Delay 
30 seconds  0 seconds  240 seconds 
Inverter 
Stacking 
Stack Mode  Master  Master, OB Slave L1, 3p Classic B , 3p Classic C 
Master Adjust Only 
0 0  7 
Power Save  
Slave Adjust Only 
1 1  15 
Grid Tie Enable  Y  Y or N 
Sell Voltage 
47.2 Vdc  40 Vdc  60 Vdc 
Grid-Tie Sell 
Grid Tie Window  IEEE  IEEE or user 
Input Voltage
11
-1 -3  1 
Output Voltage
11
-1 -3  1 
Calibrate 
Battery Voltage
12
0.0 -0.8  0.8 
11
 These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured 
value. The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it.  The result is also displayed.
12
 These values represent an adjustable setting with a range of ± 0.8 Vdc from the measured value. The range of settings allow up to 0.8 volts to be either added 
or subtracted from the measured value (in increments of 0.4 Vdc). The result is also displayed.