User Guide
Specifications
900-0112-01-00 Rev B  49 
Table 19  48-Volt Inverter Settings (MATE) 
Field Item  Default Minimum Maximum 
search sensitivity (see page 14 for increments) 
6 0  50 
search pulse length 
8 4  20 
Search
search pulse spacing 
60 AC cycles  4 AC cycles  120 AC cycles 
ac transfer control  Grid  Grid or Gen 
ac1/grid limit 
25 Aac  2.5 Aac  30 Aac 
Input
ac2/gen limit 
25 Aac  2.5 Aac  30 Aac 
low battery cut-out (LBCO) 
42 Vdc  36 Vdc  48 Vdc 
low battery cut-in (LBCI) 
50 Vdc  40 Vdc  56 Vdc 
Inverter
adjust output voltage 
230 Vac  210 Vac  250 Vac 
charger limit 
5.5 Aac  0 Aac  6 Aac 
absorb voltage 
57.6 Vdc  52 Vdc  64 Vdc 
absorb time limit 
1.0 hours  0.0 hours  24.0 hours 
float voltage 
54.4 Vdc  48 Vdc  60 Vdc 
float time period 
1.0 hours  0.0 hours  24.0 hours 
refloat voltage 
50 Vdc  48 Vdc  52 Vdc 
equalization voltage 
58.4 Vdc  56 Vdc  68 Vdc 
Charger 
equalization time period 
1.0 hours  0.0 hours  24.0 hours 
ac1/grid lower limit 
208 Vac  140 Vac  220 Vac 
ac1/grid upper limit 
252 Vac  250 Vac  280 Vac 
ac1/grid input limit 
25 Aac  2.5 Aac  30 Aac 
Grid 
ac1/grid transfer delay 
6 AC cycles  0 AC cycles  240 AC cycles 
gen input connect delay 
0.5 minutes  0.2 minutes  15 minutes 
ac2/gen lower limit 
208 Vac  140 Vac  220 Vac 
ac2/genupper limit 
252 Vac  250 Vac  280 Vac 
ac2/gen input limit 
25 Aac  2.5 Aac  30 Aac 
ac2/gen transfer delay 
6 AC cycles  0 AC cycles  240 AC cycles 
Generator 
(Gen) 
ac2/gen support  ON  ON or OFF 
aux output control  AUTO  ON, OFF, or AUTO 
aux output function  Cool Fan 
Cool Fan, DivertDC, DivertAC, AC Drop, Vent 
Fan, Fault, GenAlert, LoadShed, or Remote 
genalert on voltage 
44 Vdc  40 Vdc  56 Vdc 
genalert on delay 
4 minutes  0 minutes  240 minutes 
genalert off set point 
56 Vdc  48 Vdc  72 Vdc 
genalert off delay 
9 minutes  0 minutes  240 minutes 
load shed off voltage 
44 Vdc  40 Vdc  56 Vdc 
vent fan on set point 
52 Vdc  40 Vdc  64 Vdc 
vent fan off period 
5 minutes  0 minutes  30 minutes 
diversion on voltage 
58.4 Vdc  48 Vdc  64 Vdc 
Auxiliary 
(AUX) 
diversion off delay 
30 seconds  0 seconds  240 seconds 
Stacking
stack phase  Master  Master, OB Slave L1, 3p Classic B, 3p Classic C 
master adjust only 
0 0  7 
Power 
Save 
slave adjust only 
1 1  15 
sell re volts 
52 Vdc  40 Vdc  60 Vdc 
grid tie window  User  IEEE or User 
Sell
grid tie authority  GridTie  GridTie or No Sell 
vac input adjustment
5
236 220  254 
vac output adjustment
5
236 220  254 
Calibration 
(Cal) 
battery vdc adjustment
6
2 0  4 
5
 These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately 
1 Vac. The range of adjustment is 15 Vac above nominal and 17 Vac below nominal. 
6
 These values are in digital counts, not volts. One count equals 0.4 Vdc. The range of adjustment is 0.8 Vdc above or below nominal. 