User Guide
Installation
18  900-0111-01-00 Rev A 
Grounding
WARNING: Shock Hazard 
The unit must be connected to a grounded, permanent wiring system. If a bond is made 
between neutral and ground make sure only one bond is present in the AC system at any 
time. Some codes require the bond to be made at the main panel only. 
WARNING: Shock Hazard 
For all installations, the negative battery conductor should be bonded to the grounding 
system at only one point. If the OutBack GFDI is present, it can provide the bond. 
IMPORTANT: 
OutBack products are not designed for use in a positive-grounded system. If it is necessary 
to build a positive-ground system with OutBack products, contact OutBack Technical 
Support at 
360.618.4363
 before proceeding. Additionally, consult the online forum at 
www.outbackpower.com/forum/
, where this subject has been discussed extensively. 
Table 3  Ground Conductor Size and Torque Requirements 
Terminal Location  Minimum Conductor Size  Torque Requirements 
Center AC Terminals 
6 mm (#10 AWG or 0.008 in)  2.8 Nm (25 in-lbs) 
DC Box Lug 
16 mm (#6 AWG or 0.021 in)  5.1 Nm (45 in-lbs) 
Figure 6  DC Ground Lug 
Figure 7  AC Ground Terminals 
The inverter’s DC ground is a box lug located next to 
the negative DC battery terminal. Local codes or 
regulations may require the DC ground to be run 
separately from the AC ground. Also, if present, it will 
be necessary to remove the DC Cover before making 
the ground connection. (See the next page.) 
The two Chassis Ground/PE terminals are electrically 
common. Only one terminal can be used if 
connecting to an external ground bus. The other 
terminal may be used if connecting to a device with 
its own ground wire, such as a generator. 










