User Guide
Installation & Programming Manual FX & VFX “E” Series Inverter/Charger System  Copyright 2003  OutBack Power Systems, Inc.  
900-0027-2  19009 62
nd
 Ave NE, Arlington WA 98223 USA 
Page 54 Rev 7.1 06/08/06    Tel 360 435 6030 Fax 360 435 6019 
MATE SCREENS 
SELL MENU 
The SELL section is used to set the functions that control the process of selling power back to the utility grid. This menu is only 
operational for Grid-Tie FX’s and is not operational with “Export” FX’s at this time. These functions include setting the voltage at which 
the FX sells back to the utility grid, setting the window in which the Grid-Tie function operates, and to enable or disable the Grid-Tie 
function. The default values enable the Grid-Tie FX to sell back to the utility grid after the FX has completed a charge cycle. To 
disable this charge cycle, press the 
<AC IN> “hot” button four times, press <BULK>, press <STOP> and then press <OK>. The FX 
waits 5 minutes after it has accepted the utility grid as an AC source and must be above the “sell RE volts” (found in this menu) to start 
selling. 
ADV/FX/PAGE1-------- 
choose category: 
ADV INV CHGR PG2 
 ↓ 
ADV/FX/PAGE2-------- 
choose category: 
PG1 GRID GEN PG3 
 ↓ 
ADV/FX/PAGE3-------- 
choose category: 
PG2 AUX STACK PG4 
 ↓ 
ADV/FX/PAGE4-------- 
choose category: 
PG3 SELL CAL MAIN 
 ↓ 
ADV/FX/SELL------P00 
sell re 12.8vdc 
volts 
DOWN INC DEC PORT 
 ↓ 
ADV/FX/SELL------P00 
grid tie IEEE 
window 
DOWN IEEE USER PORT 
 ↓ 
ADV/FX/SELL------P00 
grid tie GridTie 
authority 
DOWN INC DEC PORT 
 ↓ 
ADV/FX/SELL------ 
 selling setup 
 completed 
 TOP ADV MAIN 
Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is 
displayed. Selecting
 <PG2> shows a second screen of categories. 
Selecting
 <PG3> shows a third screen of categories. 
Selecting
 <PG4> shows a fourth screen of categories. 
Selecting 
<SELL> allows adjustment of the Grid-tie and selling set points and operation. 
The 
SELL RE VOLTS (RE = Renewable Energy) screen allows the user to set the voltage at 
which they would like to sell battery power back to the utility grid. If the battery voltage is above 
the voltage shown on this screen and the FX isn’t charging then the FX will sell power back to 
the utility grid. This setting has a range between 10.0 vdc and 15.0 vdc in 0.1vdc increments. 
The 
GRID TIE WINDOW screen controls the voltage and frequency windows that the grid-tie 
function operates in. If the FX repeatedly disconnects from the utility grid this value may need to 
be changed. This function 
should not, I repeat, should not be changed without consulting 
OutBack Power Systems first. 
The 
GRID TIE AUTHORITY screen allows the user to turn on or off the selling function of the FX. 
When the screen displays “GridTie” (default), the FX will sell power under the correct conditions. 
Pressing DEC will change “GridTie” to “No Sell” and the selling function will be disabled. 
Pressing INC will change the display back from “No Sell” to “GridTie”. 
Selecting TOP returns the user to the top of the ADV/FX/SELL menu section. Selecting ADV 
returns you to the advanced screen to allow selection of another product connected to the MATE. 
Selecting MAIN returns the display to the MAIN screen. 