Outback Power FX Series Installation Manual
21
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND
NEU/GROUND BOND
AC NEUTRAL IN
AC HOT IN
FULL
OK
LOW
INVERTER
AC IN
BATTERY TEMP
MATE/HUB
INVERTER ON/OFF
INVERTER
ON/OFF
AUX+
AUX-
XCT-
XCT+
REMOVE JUMPER
TO DISABLE
GROUND SWITCHING
BATTERY
STATUS
INVERTER
STATUS
ERROR
AC HOT OUT
•  Supplies the AC hot output conductors 
through a 30 amp maximum AC branch 
rated circuit breaker using 10 AWG (.102” or 
2.59 mm) wire and connect to the AC 
AC NEUTRAL OUT/AC NEUTRAL IN
•  Connects the AC neutral input conductor to 
the AC NEUTRAL IN terminal.
•  Connects the AC neutral output conductor 
to the AC NEUTRAL OUT terminal.
•  These terminals are common in the Mobile 
FX only when an AC source is applied.
•   The NEUTRAL IN and NEUTRAL OUT 
conductors should not be common 
(connected in any way) prior to connection 
with a Mobile FX
CHASSIS GROUND
•  Connects both the AC input and AC output 
ground conductors to the CHASSIS GROUND 
and NEU/GROUND BOND terminals.
•  If there is only one Mobile FX in the system, 
leave the copper bus (provided) installed 
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more 
than one Mobile FX in the system, remove 
the copper bus from every Slave FX.
AC HOT IN 
•  The AC hot input conductor (black) must be 
supplied through a 30 amp maximum AC 
branch rated circuit breaker and connected 
to the AC HOT IN.
•  10 AWG (.102” or 2.59 mm) wire is required 
for the FX’s AC transfer switch.
 AC WIRING NOTES FOR THE MOBILE FX