7
AC AND DC GROUNDING REQUIREMENTS
• Connect only to a grounded, permanent wiring system. Ensure there is only one neutral-ground
connection in the system at any time. Some codes require this connection be made at the main
panel only.
• If the system has a generator, its neutral-ground connection will probably need to be disengaged.
• For all installations, the negative battery conductor should be bonded to the grounding system at
one (and only one) point in the system.
The FX should never be positive grounded.
The equipment ground on each is marked with this symbol:
Box lug for grounding the FX chassis