TM FW-IOB-D-120VAC Input/Output/Bypass Assembly Installation Instructions
The OutBack Power Systems FW-IOB-D-120VAC allows manual switching between the FX Series Inverter/Charger and a second AC source, facilitating maintenance and power continuity. About OutBack Power Systems OutBack Power Systems is a leader in advanced energy conversion technology. Our products include true sine wave inverter/chargers, a maximum power point charge controller, system communication components, as well as breaker panels, breakers, accessories, and assembled systems.
Requirements and Warnings The OutBack FW-IOB-D-120VAC is intended as a system component and is included in a listing by ETL as indoor enclosures to UL standard UL 508A Industrial Control Panels. This enclosure is intended for battery circuits configured for 12 to 48 volts nominal. Grounding Instructions – Each enclosure should be connected to a grounded, permanent wiring system.
FW-IOB-D-120VAC Parts List AC Breaker Bypass Slide Plate Breaker Label Set Black Terminal Bus Bar Insulators White Terminal Bus Bar Insulators AC Breakers Bus Bars Hardware Kit Ground Conductor (Green) Figure 1: FW-IOB-D-120VAC 3 Neutral Conductor (White) Positive Conductor (Black)
AC IN HOT LEG 1, BLACK INSULATORS AC OUT HOT LEG 1, BLACK INSULATORS GROUND BUS BAR AC NEUTRAL INPUT AND OUTPUT, WHITE INSULATORS NOTE: Use 10-32 X 7/16 self-tapping stainless steel fasteners to secure this hardware.
Figure 3: Sample Wiring Diagram 5
Installing the FW-IOB-D-120VAC Dual-Pole Bypass Breaker (installed upside down) Output Breakers Input Breakers Figure 4: AC Breaker Installation for FW-IOB-D-120VAC To install the FW-IOB-D-120VAC: • Remove the appropriate quantity of breaker knockouts from the breaker bracket. • Pull the yellow tabs out from each breaker. • Install the breakers on the din rail to approximately match the openings in the breaker bracket.
Installing the AC Breaker Bypass Slide Plate Figure 5: AC Breaker Bypass Slide Plate Installation Parts: 1. 8-32 X .75 Machine Screw (2) 2. Nylon Washer (4) 3. 8-32 Nylock Nut (4) 4. AC Breaker Bypass Slide Plate (1) 5. FLEXware AC Breaker Bracket (1) To Assemble: 1. Remove necessary circuit breaker knockouts (per IOB kit). 2. Install AC Breaker Bypass Slide Plate and fasteners as shown in Figure 5. 3. Do not over tighten the Nylock nuts. Overtightening can cause the AC Breaker Bypass Slide Plate to bind.