Outback Power FLEXPower Radian Series Specsheet

2
OutBack reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2017 OutBack Power. All Rights Reserved. OutBack is a registered trademark of The Alpha Group.
FLEXpower Radian SPECIFICATIONS 06/2017
Model
*
Description Inverter GSLC Bypass Inverter OCPD
**
PV OCPD
**
GFDI RTS Charge Controller
FPR-4048A
GS4048A FLEXpower Radian GS4048A GSLC175-PV1-120/240 120/240VAC 175A 80A Yes Yes (1) FLEXmax 80
FPR-8048A
GS8048A FLEXpower Radian GS8048A GSLC175-PV1-120/240 120/240VAC (2) 175A (2) 80A Yes Yes (2) FLEXmax 80
Details
FLEXpower Radian 4048A FLEXpower Radian 8048A
Finished Dimensions
H x W x D (in/cm)
47.0 x 33.5 x 9.84 / 119.4 x 85.1 x 24.9 47.0 x 33.5 x 9.84 / 119.4 x 85.1 x 24.9
Weight (lb/kg)
195 / 88.5 250 / 113.4
*All pre-wired systems include a Radian Series inverter/charger, FLEXmax 80 charge controller(s), MATE3 system display and communications, FLEXnet DC system monitor, AC and DC wiring boxes, HUB10.3 communications, surge protector and remote
temperature sensor (RTS). The FLEXpower Radian is also equipped with battery and PV array breakers, GFDI and input-output-bypass.
See individual product specsheets or product guide for full specications. **Overcurrent protective device.
8.0kVA 8.0kW 8.0kVA
6.8kW
Power Rating Notes
Inverters that specify power in VA but do not use the
unity standard Power Factor (PF) could have misleading
power specications. Volt-Amps (VA) is a total inverter
output, while Watts (W) represent the power consumed by the
electrical loads. PF, which varies by types of loads, is the ratio
of W to VA, and the dierence between the two is power in the
circuit that does no useful work. At 1.0PF (unity), all power is
used. This is the industry-standard used by OutBack Power.
Radian GS8048A Power Factor Chart
Power Factor
1.0
0.75
0.5
0.25
0.0
Industry-Standard Non-Industry Standard
0.85
Radian GS8048A Power Rating Chart
Power (VA)
20000
15000
10000
5000
0
100ms 5 sec 30 min continuous
Instantaneous Power Rating
Most stringent, massive load start GS8048A: 16970VA
Surge Power Rating
Less stringent load start GS8048A: 12000VA
Peak Power Rating
Frequent “heavy duty” load requirements GS8048A: 9000VA
Continuous Power Rating
Sustained “real world” load requirements GS8048A: 8000VA
16970VA
12000VA
9000VA
8000VA
Typical Eciency Rating
Real world eciency with variable loads GS8048A: 93%
CEC Eciency Rating
Most stringent US rating GS8048A: 92.5%
Radian GS8048A Eciency Rating Chart
Eciency
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
2kVA 4kVA 6kVA 8kVA
92.5%
(CEC)
93% (Typical)