OutBack Power Ground Fault Detector Interrupter

2
IMPORTANT SAFETY INSTRUCTIONS
KEEP THESE INSTRUCTIONS
This product is intended to be installed as part of a permanently
grounded electrical system as shown in the wiring diagrams. The
following important restrictions apply unless superseded by local or
national codes:
• Groundequipmentismarkedwiththissymbol:
• The GFDI is designed for indoor installation or installation inside a
weatherproof enclosure. It must not be exposed to rain.
• Must use a UL approved crimp lug on the cable attached to the
breaker stud.
NOTE: Outback supplies a #2 AWG ring terminal with the GFDI and
recommends a #2 AWG cable when the GFDI is connected to an 80 amp
breaker. (#3 AWG is the minimum allowable in this application.
See Standards and Requirements, page 3.)
Introduction
The OutBack Power Systems Ground Fault Detector Interrupter (GFDI) is
a safety device for a photovoltaic (PV) array. In the event that the array
becomes shorted to ground, it disconnects the PV system from the
batteries.
• The GFDI meets mandatory UL 1741 low-level ground-fault protection
requirementsforroof-mountedphotovoltaicenergysystemsto
prevent res.
• TheGFDImeetstherequirementsofthe2008NECsection
690.5 (A)
through (C) to reduce re hazards when wired
according to the wiring
diagram contained in these instructions.
OutBack GFDI Products
• OBB-GFDI-80-150VDC-PNL (one 0.5 amp breaker ganged with one
80 amp breaker with common trip)
• OBB-GFDI-80D-150VDC-PNL (one 0.5 amp breaker ganged with two
80 amp breakers with common trip)
• OBB-GFDI-80Q-150VDC-PNL (one 0.5 amp breaker ganged with four
80 amp breakers with common trip)