Installation Manual Owner's manual
Installation
AC Connections
WARNING: Fire Hazard
Multi-wire branch circuits in residential installations can create a potential fire
hazard with inverter installations. Be sure to check for multi-wire branch circuits
before making any AC connections and make any changes required to remove
the hazard.
Table 5 AC Conductor Size and Torque Requirements
AC Terminal Minimum Allowed
Conductor Size
Maximum
Conductor Size
Torque
Requirements
Breaker
Size
AC IN #14 AWG (2.1 mm
2
) 1/0 AWG (53.5 mm
2
) 35 in-lb (4 Nm) 60 Aac
AC OUT #14 AWG (2.1 mm
2
) 1/0 AWG (53.5 mm
2
) 35 in-lb (4 Nm) 60 Aac
Neutral Bus Bar #14 AWG (2.1 mm
2
) 1/0 AWG (53.5 mm
2
) 35 in-lb (4 Nm) N/A
Internal components shown may vary from model to model.
Factory wiring is not shown.
See Table 5 for recommended conductor
sizes and tor
q
ue re
q
uirements.
1
See the WARNING on
page 32 for additional
information.
Neutral-to-Ground
Bond
1
Figure 17 AC IN Connections
900-0095-01-00 Rev A
31