Table 1 OutBack Block
Start End Size R/W Field Name Type Units
Scale
Factor Contents Description
4 4 1 R
OutBack_Minor_Firmware
_Number
uint16 N/A N/A Read Only OutBack Minor firmware revision
5 5 1 R OutBack_Encryption_Key uint16 N/A N/A Read Only
Encryption key for current session (0 = Encryption not
enabled)
6 12 7 R OutBack_MAC_Address String (14) N/A N/A Read Only Ethernet MAC address
13 20 8 W OutBack_Write_Password String (16) N/A N/A Write Only Password required to write to any register
21 21 1 R/W OutBack_Enable_DHCP uint16 Enumerated N/A Programmable
0 = DHCP Disabled, use configured network
parameter; 1 = DHCP Enabled
22 23 2 R/W OutBack_TCP/IP_Address uint32 Address N/A Programmable TCP/IP Address xxx.xxx.xxx.xxx
24 25 2 R/W
OutBack_TCP/IP_Gateway
_MSW
uint32 Address N/A Programmable TCP/IP Gateway xxx.xxx.xxx.xxx
26 27 2 R/W
OutBack_TCP/IP_Netmask
_MSW
uint32 Address N/A Programmable TCP/IP Netmask xxx.xxx.xxx.xxx
28 29 2 R/W
OutBack_TCP/IP_DNS_1_
MSW uint32 Address N/A Programmable TCP/IP DNS 1 xxx.xxx.xxx.xxx
30 31 2 R/W
OutBack_TCP/IP_DNS_2_
MSW
uint32 Address N/A Programmable TCP/IP DNS 2 xxx.xxx.xxx.xxx
32 32 1 R/W OutBack_Modbus_Port uint16 N/A N/A Programmable OutBack MODBUS IP port, default 502
33 52 20 R/W
OutBack_SMTP_Server_
Name
String (40) N/A N/A Programmable Email server name
53 68 16 R/W
OutBack_SMTP_Account_
Name String (32) N/A N/A Programmable Email account name
69 69 1 R/W
OutBack_SMTP_SSL_
Enable
uint16 Enumerated N/A Programmable 0 = SSL Disabled; 1 = SSL Enabled (not implemented)
70 77 8 W
OutBack_SMTP_Email_
Password
String 16) N/A N/A Write Only Email account password
78 97 20 R/W
OutBack_SMTP_Email_
User_Name
String (40) N/A N/A Programmable Email account User Name
98 98 1 R/W
OutBack_Status_Email_
Interval
uint16 N/A N/A Programmable
0 = Status Email Disabled, 1-23 Status Email every n
hours
99 99 1 R/W
OutBack_Status_Email_
Status_Time uint16 N/A N/A Programmable Hour of first status email of the day
100 124 25 R/W
OutBack_Status_Email_
Subject_Line
String (50) N/A N/A Programmable Status Email Subject Line
125 144 20 R/W
OutBack_Status_Email_To
_Address_1
String (40) N/A N/A Programmable Status Email to Address 1
145 164 20 R/W
OutBack_Status_Email_To
_Address_2
String (40) N/A N/A Programmable Status Email to Address 2
165 165 1 R/W
OutBack_Alarm_Email_
Enable
uint16 Enumerated N/A Programmable 0 = Disabled; 1 = Enabled
166 190 25 R/W
OutBack_Alarm_Email_
Subject_Line String (50) N/A N/A Programmable Status Alarm_Subject Line
191 210 20 R/W
OutBack_Alarm_Email_To_
Address_1
String (40) N/A N/A Programmable Status Alarm to Address 1
211 230 20 R/W
OutBack_Alarm_Email_To_
Address_2
String (40) N/A N/A Programmable Status Alarm to Address 2
231 238 8 W OutBack_FTP_Password String (16) N/A N/A Write Only FTP password
239 246 8 W OutBack_Telnet_Password String (16) N/A N/A Write Only Telnet password (not implemented)
247 247 1 R/W
OutBack_SD_Card_Data_
Log_Write_Interval
uint16 N/A N/A Programmable 0 = SD-Card Data Logging disabled, 1-60 seconds
248 248 1 R/W
OutBack_SD_Card_Data_
Log_Retain_Days
uint16 N/A N/A Programmable
0 = Log until SD-Card is full then erase oldest, 1-731
Number of days to retain data logs
249 249 1 R/W
OutBack_SD_Card_Data_
Logging_Mode
uint16 Enumerated N/A Programmable 0 = Disabled; 1 = Excel Format; 2 = Compact Format
250 269 20 R/W
OutBack_Time_Server_
Name String (40) N/A N/A Programmable Timeserver domain name
270 270 1 R/W
OutBack_Enable_Time_
Server
uint16 Enumerated N/A Programmable
0 = Time Server Disabled, use configured time
parameters; 1 = Time Server Enabled
271 271 1 R/W OutBack_Set_Time_Zone int16 Hours N/A Programmable Time Zone -12-11
272 272 1 R/W OutBack_Year uint16 N/A N/A Programmable Clock year (4 digit)
273 273 1 R/W OutBack_Month uint16 N/A N/A Programmable Clock Month (1 - 12)
274 274 1 R/W OutBack_Day uint16 N/A N/A Programmable Clock Day (1 - 31)
275 275 1 R/W OutBack_Hour uint16 N/A N/A Programmable Clock Hour (0 - 23)
276 276 1 R/W OutBack_Minute uint16 N/A N/A Programmable Clock Minute (0 - 59)
277 277 1 R/W OutBack_Second uint16 N/A N/A Programmable Clock Second (0 - 59)
278 278 1 R OutBack_Temp_Batt int16 Degrees C N/A Measured Battery temp in degrees C
279 279 1 R OutBack_Temp_Ambient int16 Degrees C N/A Measured
Ambient temp from temp sensor connected to
device, in degrees C
280 280 1 R OutBack_Temp_SF int16 N/A N/A 0 Temperature Scale Factor
281 281 1 R OutBack_Error uint16 Bitfield N/A Read Only Bit field for errors. See Table 6 on page 3.
282 282 1 R OutBack_Status uint16 Bitfield N/A Read Only Bit field for status. TBD.
283 283 1 N/A OutBack_Spare_Register_1 uint16 N/A N/A N/A For future use