- Outback Power Auto Transformer Installation Manual
4
Grounding Instructions 
• The FW-X240’s metal mounting bracket must be connected to a permanently grounded 
system. System grounding as required by the National Electric Code, ANSI /NFPA 70-1996, is the 
responsibility of the system installer. 
•  The FW-X240 hardware kit includes grounding washers to penetrate a powder-coated  nish, 
assuring a proper ground connection to any FLEXware enclosure or mounting plate.
• An installation might call for an optional grounding wire between the FW-X240 and the FLEXware 
enclosure or mounting plate to which it’s attached depending on local code requirements or the 
nature of the installation itself.
Connections
•  No additional terminals or lugs are required for hook-up of the AC wiring. 
•  AC wiring must be no less than 10 AWG gauge copper wire, rated for 75 degrees C or higher and 
must be sized appropriately to the circuit breaker.
Hardware Kit
The FW-X240 comes with four M6 X 20 mm screws, four  at washers, and four grounding washers for 
mounting to a FLEXware Mounting Plate from inside a FLEXware AC enclosure. 